c. Extend the AC supply leads with the extension wires supplied
(follow the electrical wiring in Figure 4).
d. Route the supplied wires through the center hole of the spider
plate.
e. Fasten the spider plate to the junction box using the junction box
screws(3).
f.
Feed wires into the unit through the center hole of canopy.
g. Fasten the canopy-housing assembly to the spider plate using
the screws provided(6).
5. For remote power DC units, connect the red wire to the positive of the
DC supply and the blue to the negative (6 to 24VDC).
6. Make the proper connections, our system accepts an input voltage of
120 to 277 VAC (see figure. 4). Connect the purple and white leads to
the building utility. Connect the green ground wire to the service
ground or the ground connection in the junction box.
7.
AC/DC or AC only models:
When AC is energized the LED strip will
light.
For self-powered models only
a. When ready to energize AC, plug in battery connector to circuit
board. Connect battery and turn on AC power within 6 hours.
b. When AC is energized the LED strip will light and green pilot light
will illuminate. Allow 24 hours charge before initial duration test-
ing.
8. Replace cover by squeezing it a little bit and pushing down. Secure
the cover with the appropriate screws(8).
9. Reconnect the AC power.
Testing (self-powered models only)
Operate test switch: Press switch-”AC on” pilot light will turn off
- Release switch- “AC on” pilot will turn on
- Legend remains lit during testing.
Maintenance
None required. Unit should be tested monthly in accordance with safety
codes and local codes. If AC supply to the unit is to be disconnected for
2 months or more, the battery must be disconnected.
1
2
3
4
5
6
9
8
10
11
12
7
Figure 2
Plugs
1
2
3
4
5
6
7
9
10
11
12
8
Figure 3
Knockout
White- neutral
Red DC+
Blue DC-
Canopy
Battery*
(self-powered only)*
LED strip
DC supply
(AC/DC
Figure 4
Switch*
AC on (pilot)*
Purple-AC 120 to 277VAC
Green- ground
{
AC supply leads
}
(6 to24v DC)
models only)
Note:
Final connections
are to be made inside
unit using extension