background image

Types 1301F and 1301G

D100341X012

Instruction Manual

Form 1111

September 2015

www.fisherregulators.com

!

WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fire and/or chemical contamination 

causing property damage and personal 

injury or death.
Fisher

®

 regulators must be installed, 

operated and maintained in accordance 

with federal, state and local codes, rules 

and regulations and Fisher instructions.
If the regulator vents gas or a leak 

develops in the system, service to the unit 

may be required. Failure to correct trouble 

could result in a hazardous condition.
Installation, operation and maintenance 

procedures performed by unqualified 

personnel may result in improper 

adjustment and unsafe operation. Either 

condition may result in equipment 

damage or personal injury. Use qualified 

personnel when installing, operating 

and maintaining the 1301 Series high-

pressure regulator.

Introduction

Scope of the Manual

This Instruction Manual provides instructions for the 

installation, adjustment, maintenance and parts ordering 

of the Types 1301F and 1301G high-pressure regulators.

Product Description

Types 1301F and 1301G regulators are direct-operated, 

high-pressure regulators, which can be used where 

high-pressure gas must be reduced for use as pilot 

supply pressure in pilot-operated regulators or as 

loading pressure in pressure-loaded regulators. 

1301 Series High-Pressure Regulators

Types 1301F and 1301G regulators can also be used 

in many other applications due to their rugged design 

as high-pressure reducing regulators for various fluids 

such as air, gas, water and other liquids.
The Type 1301F can handle outlet pressures from 10 to 

225 psig / 0.69 to 15.5 bar in three ranges and the 

Type 1301G can handle outlet pressures from 200 to 

500 psig / 13.8 to 34.5 bar in one range.

Figure 1.

 Type 1301F High-Pressure Regulator

P1025

Summary of Contents for 1301G

Page 1: ...alified personnel when installing operating and maintaining the 1301 Series high pressure regulator Introduction Scope of the Manual This Instruction Manual provides instructions for the installation adjustment maintenance and parts ordering of the Types 1301F and 1301G high pressure regulators Product Description Types 1301F and 1301G regulators are direct operated high pressure regulators which ...

Page 2: ...ef Valve Sizing Cg 5 0 Cv 0 13 C1 38 5 Specifications Specifications section lists the specifications for Types 1301F and 1301G high pressure regulators The maximum outlet pressure for a given regulator as it comes from the factory is stamped on the regulator nameplate IEC Sizing Coefficients XT 0 938 FD 0 50 FL 0 85 Recovery Coefficient Km 0 72 Material Temperature Capabilities 1 Nylon PA Valve D...

Page 3: ...ring force which is sensed by the diaphragm moving the yoke and disk assembly up near its orifice restricting flow across the regulator M1015 INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE Type 1301F Figure 2 Type 1301F Operational Schematic TYPE OUTLET PRESSURE RANGES 1 SPRING COLOR SPRING PART NUMBER SPRING WIRE DIAMETER SPRING FREE LENGTH psig bar In mm In mm 1301F 10 to 75 0 69 to 5 2 Blu...

Page 4: ...ator spring range If pressure adjustment is necessary refer to the Startup section In all cases check the spring setting to make sure it is correct for the application Overpressure Protection The 1301 Series regulators have an outlet pressure rating lower than their inlet pressure rating If actual inlet pressure can exceed the outlet pressure rating outlet overpressure protection is necessary Howe...

Page 5: ...alves are a matched set and need to be kept together 10 Unscrew the orifice key 5 Examine seating edge of orifice Replace with a new part if worn or nicked Assembly This procedure assumes that the regulator was completely disassembled If not start these instructions at the appropriate step Key numbers used are shown in Figure 3 for the Type 1301F regulator and in Figure 4 for the Type 1301G regula...

Page 6: ...e Regulator Assembly 15 2 11 19 16 1 13 14 3 22 10 6 5 4 12 17 7 8 9 18 CN7095_C 6 15 2 11 19 16 1 13 14 3 22 10 5 4 12 17 7 8 9 18 21 19 8 7 17 4 13 BP6341 A Figure 5 Exploded View of The Diaphragm Head Assembly and Yoke 20 40 S 6 0 0 0 P S I M A X I N L E T F I S H E R M AX OUTLET PSI U S A NOTE OPTIONAL THIRD OUTLET ...

Page 7: ...d Type 1301G 1 8 NPT vent connection Standard or with T Handle Brass 2P195713022 316 Stainless steel 21A6377X012 3 Bottom Cap Brass 1D468513012 304 Stainless steel 1J919635072 316 Stainless steel NACE 1J9196X0032 4 Yoke Brass 1D383313012 316 Stainless steel NACE 1J925936042 5 Orifice 303 Stainless steel 1D386535032 316 Stainless steel NACE 1D3865X0032 6 Valve Disk Assembly Brass Nylon PA 1D4684000...

Page 8: ... Headquarters Elk River Minnesota 55330 2445 USA Tels 1 763 241 3238 1 800 447 1250 Europe Selmsdorf 23923 Germany Tel 49 38823 31 287 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9499 For further information visit www fisherregulators com Key Description Part Number 17 Machine Screw 2 required Steel for brass yoke 1H526928982 302 Stainless steel for Stainless steel yoke 1J926938992 18 Locknu...