background image

5

4)

4)

4)

4)

4) Select Energy Management Recovery OFF or ON

Select Energy Management Recovery OFF or ON

Select Energy Management Recovery OFF or ON

Select Energy Management Recovery OFF or ON

Select Energy Management Recovery OFF or ON -
Energy Management Recovery (EMR) causes the thermo-
stat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start 5 minutes early for every 1° of
temperature required to reach setpoint.

Example:

Example:

Example:

Example:

Example:  You select EMR and have your heating pro-
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65° the difference between 65° and 70° is
5°. Allowing 5 minutes per degree the thermostat setpoint
will change to 70° at 6:35 AM. Cooling allows more time per
degree because it takes longer to reach temperature.

5)

5)

5)

5)

5) Select filter replacement run time

Select filter replacement run time

Select filter replacement run time

Select filter replacement run time

Select filter replacement run time - The thermostat will
display  “FLTR” 

“FLTR” 

“FLTR” 

“FLTR” 

“FLTR”  after a set time of operation. This is a

reminder to change or clean your air filter. This time can be
set from 0 to 1950 hours in 50 hour increments. A selection

A selection

A selection

A selection

A selection

of 000 will cancel this feature.

of 000 will cancel this feature.

of 000 will cancel this feature.

of 000 will cancel this feature.

of 000 will cancel this feature. When “FLTR”

“FLTR”

“FLTR”

“FLTR”

“FLTR” is displayed,

you can clear it by pressing HOLD and RUN at the same
time. This resets the timer and starts counting the hours
until the next filter change. Changing the time in the menu
also resets the timer.

6)

6)

6)

6)

6) Select Compressor Lockout LOC OFF or ON

Select Compressor Lockout LOC OFF or ON

Select Compressor Lockout LOC OFF or ON

Select Compressor Lockout LOC OFF or ON

Select Compressor Lockout LOC OFF or ON - Selecting
LOC ON will cause the thermostat to wait 5 minutes before
turning on the compressor if the heating and cooling sys-
tem loses power. It will also wait 5 minutes minimum
between cooling cycles. This is intended to help protect the
compressor from short cycling. Some newer compressors
already have a time delay built in and do not require this
feature. Your compressor manufacturer can tell you if the
feature is already present in their system. When the com-
pressor time delay occurs it will flash the (snowflake icon)
for about five minutes then turn on the compressor.

7)

7)

7)

7)

7) Select Temperature Display Adjustment 4 LO to 4 HI

Select Temperature Display Adjustment 4 LO to 4 HI

Select Temperature Display Adjustment 4 LO to 4 HI

Select Temperature Display Adjustment 4 LO to 4 HI

Select Temperature Display Adjustment 4 LO to 4 HI -
Allows you to adjust the room temperature display 4° higher
or lower. Your thermostat was accurately calibrated at the
factory but you have the option to change the display
temperature to match your previous thermostat.

8)

8)

8)

8)

8) Select F° or C° Readout

Select F° or C° Readout

Select F° or C° Readout

Select F° or C° Readout

Select F° or C° Readout - Changes the display readout to
Centigrade or Fahrenheit as required.

OPERATING FEATURES

OPERATING FEATURES

OPERATING FEATURES

OPERATING FEATURES

OPERATING FEATURES

Now that you are familiar with the thermostat buttons and
display, read the following information to learn about the many
features of the thermostat.

• SIMULTANEOUS HEATING/COOLING PROGRAM

SIMULTANEOUS HEATING/COOLING PROGRAM

SIMULTANEOUS HEATING/COOLING PROGRAM

SIMULTANEOUS HEATING/COOLING PROGRAM

SIMULTANEOUS HEATING/COOLING PROGRAM
STORAGE 

STORAGE 

STORAGE 

STORAGE 

STORAGE — When programming, you can enter both
your heating and cooling programs at the same time. There
is no need to reprogram the thermostat at the beginning of
each season.

• TEMPERATURE OVERRIDE

TEMPERATURE OVERRIDE

TEMPERATURE OVERRIDE

TEMPERATURE OVERRIDE

TEMPERATURE OVERRIDE — Press 

 or 

 until the

display shows the temperature you want. The thermostat
will override current programming and keep the room
temperature at the selected temperature until the next
program period begins. Then the thermostat will automati-
cally revert to the program.

• HOLD TEMPERATURE

HOLD TEMPERATURE

HOLD TEMPERATURE

HOLD TEMPERATURE

HOLD TEMPERATURE — The thermostat can hold any
temperature within its range for an indefinite period without
reverting to the programmed temperature. Momentarily
press HOLD button. “HOLD”

“HOLD”

“HOLD”

“HOLD”

“HOLD” will be displayed. Then choose

the desired temperature by pressing 

 or 

. The

thermostat will hold the room temperature at the selected
setting until you press RUN button to start program opera-
tion again.

• CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU — Allows you to customize
certain thermostat options.

PROGRAMMING YOUR THERMOSTAT

PROGRAMMING YOUR THERMOSTAT

PROGRAMMING YOUR THERMOSTAT

PROGRAMMING YOUR THERMOSTAT

PROGRAMMING YOUR THERMOSTAT

This section will help you plan your thermostat’s program to
meet your needs. For maximum comfort and efficiency, keep
the following guidelines in mind when planning your program.

• When heating (cooling) your building, program the

temperatures to be cooler (warmer) when the building is
vacant or during periods of low activity.

• During early morning hours, the need for cooling is

usually minimal.

1

  Step 

Press Button(s) 

Displayed (Factory Default)    Press          or          to select:            

COMMENTS

HOLD

(0:00)

0 to 8 hrs (in 

15 minute increments)

2

(FA)

SL

Select temporary Hold time

4

5

E

(ON)

OFF

6

7

 LOC

(OFF)

ON

0 HI

(0)

4 LO to

4 HI

(F)

C

Returns to normal operation

8

9

Select Energy Management Recovery OFF or ON

Select compressor lockout OFF or ON

Select temperature display adjustment higher or lower

Select temperature display to  F or  C

RUN

PRGM

and

 RUN

HOLD

*

HOLD

*

3

d-L

(ON)

OFF

Select display 

b

acklight OFF or ON

HOLD

*

HOLD

*

Filter

(000)

0 to 1950 hours

(in 50 hour increments)

Select filter replacement run time

HOLD

*

HOLD

*

HOLD

*

Select FA or SL (Fast or Slow) heating cycle rate

Configuration Menu

* Press 

HOLD to advance to next item or TIME to move 

b

ackwards to previous item

Summary of Contents for 1F80-361

Page 1: ...e on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Higher voltage will damage control and could cause Higher voltage will damage control and could cause Higher voltage will damage control and could cause H...

Page 2: ... THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL 1 Remove the packing material from the thermostat Gently pull the cover straight off the base Forcing or prying on the thermostat will cause damage to the unit If necessary move the electric heat switch see ELECTRIC HEAT SYSTEMS ELECTRIC HEAT SYSTEMS ...

Page 3: ...g Valve RC O B C JUMPER WIRE Compressor Contactor JUMPER WIRE Reversing valve is energized when the system switch is in the HEAT position Fan Relay The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year with fresh premium brand alkaline batteries Heating System Heating System Heating System Heating System Heating System 1 Move SYSTE...

Page 4: ...Press RUN to make sure the thermostat is in the run program mode then press PRGM and RUN at the same time to enter the configuration menu The display will show the first item in the configuration menu The configuration menu table summarizes the configuration options An explanation of each option follows OPERATION OPERATION OPERATION OPERATION OPERATION Press HOLD to change to the next menu item or...

Page 5: ...emperature to match your previous thermostat 8 8 8 8 8 Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Changes the display readout to Centigrade or Fahrenheit as required OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES Now that you are familiar with the thermostat buttons and display read t...

Page 6: ...mmed times and tempera tures follow these steps Determine the time periods and temperatures for your weekday and weekend programs You must program four periods for both the weekday and weekend program However you may use the same heating and cooling temperatures for consecutive time periods You can choose start times heating tempera tures and cooling temperatures independently for both week day an...

Page 7: ...rmo stat by pressing and TIME at the same time This also resets the factory defaults to the configuration menu and Symptom Symptom Symptom Symptom Symptom P P P P Possib ossib ossib ossib ossible Cause le Cause le Cause le Cause le Cause Corrective Action Corrective Action Corrective Action Corrective Action Corrective Action No Heat No Cool No Fan No Heat No Cool No Fan No Heat No Cool No Fan No ...

Page 8: ...einfluencingthe adjusted Contactalocalservicepersonfor cyclerate suggestions Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer 1 Thermostatthermometersettingrequires Thethermometercanbeadjusted 4degreesas Disagree Disagree Disagree Disagree Disagree adjustment listedinitem7o...

Page 9: ... o por un electricista autorizado No exceda los valores nominales especificados Todas las conexiones eléctricas deben cumplir con los códigos y reglamentaciones locales y nacionales Este control es un instrumento de precisión y debe manipularse con cuidado Lamanipulacióndescuidadaoladistorsióndeloscomponentes podrían hacer que el control no funcionara correctamente PRECAUCIÓN Para evitar descargas...

Page 10: ...a unidad Si es necesario mueva el interruptor de calor eléctrico vea la sección SISTEMAS DE CALOR ELÉCTRICOS más arriba 2 Conecte los cables que se encuentran debajo de los tornillos terminales a la base consultando el esquema de conexiones apropiado vea las figuras 2 a 7 3 Coloquelabasesobreelorificiodelaparedymarquelasubicaciones de los orificios de montaje usando la base como plantilla 4 Mueva ...

Page 11: ...r CABLE DE PUENTE La válvula inversora se energiza cuando el interruptor del sistema está en la posición COOL Relé del ventilador SISTEMA TERMOSTATO Vivo Neutro RH Y 24 VCA 120 VCA Vivo Neutro G W Figura 7 Diagrama de conexiones típico para una bomba de calor con válvula inversora energizada en HEAT TRANSFORMADOR Válvula inversora RC O B C CABLE DE PUENTE Contactor del compresor CABLE DE PUENTE La...

Page 12: ...en el menú de configuración La pantalla mostrará la primera opción del menú de configuración En la tabla del menú de configuración se resumen las diferentes opciones de configuración disponibles seguidas por una explicación de cada una OPERACIÓN Presione HOLD para pasar a la siguiente opción del menú o presione TIME para volver a la opción anterior Para salir del menú y volver a la operación del p...

Page 13: ...s centígrados o Fahrenheit según su preferencia FUNCIONES DEL TERMOSTATO Ahoraqueestáfamiliarizadoconlosbotonesdeltermostatoylapantalla lea la siguiente información para conocer las diferentes funciones del termostato ALMACENAMIENTO SIMULTÁNEO DE PROGRAMAS DE CALEFACCIÓN REFRIGERACIÓN Cuando programe el termostato puede ingresar sus programas de calefacción y refrigeración al mismo tiempo No es ne...

Page 14: ...mine las horas y temperaturas para sus programas semanales y de fines de semana Debe programar cuatro períodos para el programa semanal y cuatro para el programa de fin de semana No obstante puede usar las mismas temperaturas de calefacción y refrigeración durante períodos consecutivos Puede elegir las horas de inicio las temperaturas de calefacción y las temperaturas de refrigeración de maneraind...

Page 15: ...enda cambiar las pilas una vez al año por pilas alcalinas nuevas AA Síntoma Causa posible Acción correctiva El sistema no calienta El sistema no enfría No funciona el ventilador problemas comunes 1 Se quemó el fusible o se disparó el disyuntor 2 El interruptor de alimentación de la caldera está en OFF 3 La puerta o el panel del compartimiento del soplador de la caldera están sueltos o no están bie...

Page 16: ...los de refrigeración son demasiado cortos o demasiado largos oscilación reducida o amplia de la temperatura 1 La ubicación del termostato y el tamaño del sistema de refrigeración pueden influir en la duración del ciclo La duración del ciclo de refrigeración es fija y no se puede ajustar Póngase en contacto con personal de servicio local para que le sugiera otras soluciones El ajuste del termostato...

Reviews: