5.  Slowly open the downstream block valve. 
6.  Slowly close the bypass valve, if used. 
7.  Check all connections for leaks. 

note

the type VsX2 is not interchangeable 

with the type VsX8 module. Each slam-

shut module requires a mating valve 

body. Both slam-shut and body can be 

replaced in the field. see parts list for 

part numbers.

299H series adjustment 

Keys are referenced in Figure 2. The only adjustment 

on a 299H Series regulator is the reduced pressure 

setting of the pilot control spring (key 32). Remove 

the closing cap (key 29) and turn the adjusting screw 

(key 36). Turning the adjusting screw clockwise into 

the spring case increases the controlled or reduced 

pressure setting. Turning the screw counterclockwise 

decreases the reduced pressure setting. Always 

tighten the locknut (key 35) and replace the closing 

cap after making adjustments.

note

It is recommended that the 299H series 

regulators use a complete matching 

casing set that includes an upper case, 

a lower case and spring case in the 

old blank configuration or new swirl 

configuration. However, these parts are 

interchangeable with each other.

Taking Out of Service (Shutdown)

!

WarnIng

to avoid personal injury resulting from 

sudden release of pressure, isolate 

the regulator from all pressure before 

attempting disassembly.
the seal and warning tag contain 

important safety information, if removed 

be sure to reattach before startup.

BoDy sIzE

BoDy MatErIal anD EnD ConnECtIon stylE

Dn

In.

Cast Iron  

(For types 299H and 299Hr only)

Ductile Iron

steel  

(For types 299H and 299Hr only)

- - - -

1-1/4

NPT

- - - - 

- - - -

- - - -

1-1/2

NPT

NPT

NPT

50

2

NPT and CL125 FF

(1)

 flanged

NPT, CL125 FF, CL250 RF flanged and 

PN 10/16 flanged

NPT and CL150 RF flanged

1. This flange is available with a face-to-face dimension of 191 mm / 7.5 in. or 254 mm / 10 in.

Table 1.

 Body Sizes and End Connection Styles

outlEt (Control) PrEssurE rangE

tyPE

mbar

In. w.c.

299H

299Hr, 299HV and 299HVr

9 to 15

(1)

 

12 to 22

(1)

 

17 to 50

(1)

 

40 to 99

(1)

3.5 to 6

(1)

  

5 to 9

(1) 

7 to 20

(1)  

16 to 40

(1)

X

X

X

X

X

X

X

X

69 mbar to 0.22 bar  

0.19 to 0.41 bar  

0.35 to 1.1 bar   

0.97 to 2.4 bar  

2.1 to 4.1 bar  

1 to 3.25 psig  

2.75 to 6 psig 

5 to 16 psig  

14 to 35 psig  

30 to 60 psig

X

X

X

X

X

X

X

X

- - - - 

- - - - 

1. Use a pilot supply regulator if actual inlet pressure varies more than ±1.4 bar / 20 psi and the published accuracy is required.

Table 2.

 Outlet Pressure Ranges

Parts list

299H Series Regulator 

Key Description 

  1 

Lower Casing, Types 299H, 299HV and 299HVR

  2 

Upper Casing, Type 299HV

  3 

Closing Cap

  4 

Spring Seat Delrin

®

 (standard)

 

Steel (High vibration or engine applications - used with key 93)

  5 

Adjustment Nut

  6 

Closing Spring

  7 

Pressure Equalization Spring

 8*  Diaphragm

 9*  O-ring

  10  Diaphragm Post

  11  Pusher Post

 12  Orifice

 13*  Disk

 14*  O-ring

 15*  O-ring

  16  Valve Stem Assembly

  17  Valve Body

  18  Cap Screw

  19   Elbow (3 required for Cast Iron or Steel bodies; 2 required for 

Ductile Iron Bodies)

*Recommended spare part.

Delrin

®

 is a mark owned by E.I. du Pont de Nemours and Co.

299H Series

3

Summary of Contents for 299HV

Page 1: ... Inlet Pressure by Orifice Size 1 6 4 x 9 5 mm 1 4 x 3 8 in 12 1 bar 175 psig 9 5 mm 3 8 in 12 1 bar 175 psig 13 mm 1 2 in 12 1 bar 175 psig 19 mm 3 4 in 10 3 bar 150 psig 22 mm 7 8 in 3 8 6 bar 125 psig 25 mm 1 in 3 6 9 bar 100 psig 30 mm 1 3 16 in 3 5 5 bar 80 psig Maximum Casing and Emergency Outlet Pressure 1 4 5 bar 66 psig Proof Test Pressure All Pressure Retaining Components have been proof...

Page 2: ...ent installed downstream of Type VSX8 slam shut device can be damaged if the following procedure for resetting the Type VSX8 slam shut device is not followed This equipment includes the integral Type VSX8 regulator configurations Before proceeding with the adjustment of the slam shut device springs the operator must ensure upstream and downstream valves are closed and adjusting screws are unscrewe...

Page 3: ...eattach before startup BODY SIZE BODY MATERIAL AND END CONNECTION STYLE DN In Cast Iron For Types 299H and 299HR only Ductile Iron Steel For Types 299H and 299HR only 1 1 4 NPT 1 1 2 NPT NPT NPT 50 2 NPT and CL125 FF 1 flanged NPT CL125 FF CL250 RF flanged and PN 10 16 flanged NPT and CL150 RF flanged 1 This flange is available with a face to face dimension of 191 mm 7 5 in or 254 mm 10 in Table 1...

Page 4: ...al Registration 1 required for Dual Registration 57 Lever 58 Pipe Plug 59 Pipe Plug Internal Registration only 61 O ring 2 required for External Registration 1 required for Dual Registration 62 Drive Screw 63 Nameplate 68 Wire Seal 69 Warning Tag 70 Bleed Restriction 72 Filter Assembly 78 Pilot Supply Tubing Long for constructions with filter or pilot supply option 79 Pilot Supply Tubing Short for...

Page 5: ... POLYTETRAFLUOROETHYLENE PTFE THREAD SEALANT S1 Type 299hR PILOT WITH TOKEN rELIEF vALVE T80391 6 40 43 42 38 28 29 A 32 34 36 35 33 37 39 40 43 37 28 41 42 34 36 35 33 32 38 44 88 41 44 39 A L2 29 L2 Figure 2 299H Series Pilot Assemblies Type 299h PILOT WITHOUT rELIEF vALVE T80391 6 40 43 42 38 28 29 A 32 34 36 35 33 37 39 40 43 37 28 41 42 34 36 35 33 32 38 44 88 41 44 39 A L2 29 L2 apply anti s...

Page 6: ...1 10 9 S2 L1 L1 A L1 3 4 NPT DOWNSTREAM CONTROL LINE CONNECTION L2 T80391 T80391 7 299H Series Pilot Trim SEE FIGURE 3 45 25 57 56 48 53 52 54 49 51 50 70 L2 L1 L1 L1 L2 L2 APPLY MULTI PURPOSE LUBRICANT L1 ANTI SEIZE COMPOUND L2 THREAD LOCK SEALANT S2 ADHESIVE A 299H Series 6 ...

Page 7: ... 5 299H Series Exterior Assembly 84 85 86 87 20 21 19 18 17 29 89 31 19 30 47 58 20 46 22 19 62 63 21 2 23 1 69 68 3 L2 S1 S1 S1 S1 S1 S1 APPLY ANTI SEIZE COMPOUND L2 MULTI PURPOSE PTFE THREAD SEALANT S1 299H Series 7 ...

Page 8: ...14 2002 2019 Emerson Process Management Regulator Technologies Inc All rights reserved 01 19 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes...