The UPS cabinets are fitted with castors on the base to allow ease of
movement and positioning, When the equipment has been finally
positioned ensure the adjustable feet are sat so that the UPS will
remain stationary and stable (see figure 3-2)
The UPS can be lifted using either a fork lift, or a cradle. Take care
when using either method not to damage the UPS castors or jacking
foot located on the bottom of the unit.
WARNING
Ensure that the UPS weight is within the designated S.W.L.
of any handling equipment. See the UPS specification for
weight details.
Do not move the battery cabinet with the batteries fitted.
The UPS module should be located in a cool, dry, clean-air
environment with adequate ventilation to keep the ambient
temperature within the specified operating range. Where ventilation is
poor and ambient temperature is high, a system of extractor fans
should be installed to mid cooling-air flow, and a suitable air filtration
system used where the UPS is to operate in a dirty environment.
Cables:
All control cables should be screened and run separate from the
power cables, in metal conduits or metal ducts which are electrically
bonded to the metalwork of the cabinets to which they are connected.
Cooling air-flow:
All the models in the 7400-M range are force-cooled with the aid of
Internal fans. Cooling air enters the module through ventilation grills
located at the bottom of the front doors and is exhausted through the
fan grills located on the rear panel; you must therefore allow for a
minimum gap of 250 mm behind the unit to allow adequate air flow
(see figure 3-1).
Clearances
Clearance around the front of the equipment should be sufficient to
enable free passage of personnel with the doors fully opened.
3.1.2 Raised Floor
Installation
The equipment is to be located on a raised floor it should be mounted
on a pedestal suitably designed to accept the equipment point
loading. The Installation diagrams accompanying the system identify
the location and equipment through which the cabinet can be secured
to the floor.
3. 3.1.1 Equipment Positioning
and Environmental
considerations