Serial Line Cable Connection

The serial line cable can be 3-wire plus shielding, with a minimum section of 0.5 sq mm (for example, Belden 8772). This cable is recommended for its tech-

nical characteristics and because it maintains the quality of the electrical signal. The shield wire should be clipped.

Firmware Upgrade - Remote Access

1. Download the latest firmware update file (for example, “SS_2.02F08_Firmware_Update) to a location on your PC.
2. Connect a standard Ethernet cable from the Site Supervisor (

ETH 0

 port) to a router and enter the Site Supervisor IP address into 

a browser.

3. Login and select 

Configure System>File Management

 from the main menu.

4. Before proceeding with the firmware update, click 

Backup

 (to back up configuration files).

5. Once the backup is complete, click 

Upgrade Firmware

 and click 

Select

. Browse and locate the latest firmware update file. Select 

the file and click Open or double-click the file to load. 

6. A 

Loading file

 message will appear (wait for several seconds). Once loaded, the Revision and File Size will display. 

7. Click 

Upgrade

. A progress bar will appear with the percentage completed. The system will reboot and restart automatically 

when the upgrade is complete. 

Note that both the Display and Site Supervisor firmware will be updated simultaneously

.

8. The new firmware version number will appear in the lower right corner of the screen.
9. Note that all setpoints and configurations will remain the same. If there are discrepancies, use the backup file to restore previous 

settings.

Firmware Upgrade - USB Drive

1. Copy the latest firmware update file (for example, “SS_2.02F08_Firmware_Update) to the root folder of a USB thumb drive (the 

USB thumb drive must be format FAT16). 

2. Verify the Display is completely powered up. Plug the USB thumb drive into the USB port (located on the back of the Display). An 

Application update?

 message will appear.

3. Touch 

OK

 on the Display and the update will start. Audible tones will sound immediately to indicate the firmware has successfully 

updated.

4. Remove the USB thumb drive.

5. Touch the system configuration icon 

 and 

PRODUCT INFO

 to view the Site Supervisor and the Display version numbers to 

verify the update.

Summary of Contents for 818-9022

Page 1: ...om those described in this guide It cannot be used as a safety device Check the application limits before proceeding Emerson Retail Solutions reserves the right to change the composition of its products even without notice ensuring the same and unchanged functionality When using an external power supply it is necessary to separate the power of the device from the rest of the electrical devices con...

Page 2: ...lay base as a template 3 Move the base out of the way and drill the mounting holes If the mounting holes are too large and do not allow the base to be tightened securely use the plas tic screw anchors to secure the base 4 Fasten the base snugly to the wall using the mount ing holes shown in the figure above and two mount ing screws Leveling is for appearance only and will not affect Display operat...

Page 3: ...updates Electrical Connections Observe the connection polarity of the Display A wrong connection can cause malfunctioning and possible damage to the controller or the Dis play An external power supply is necessary to separate the power of the device from the rest of the electrical devices connected inside the electrical panel The secondary of the transformer must never be connected to earth ground...

Page 4: ...datefile Select the file and click Open or double click the file to load 6 A Loading file message will appear wait for several seconds Once loaded the Revision and File Size will display 7 Click Upgrade A progress bar will appear with the percentage completed The system will reboot and restart automatically when the upgrade is complete Note that both the Display and Site Supervisor firmware will b...

Page 5: ...erson Climate Technologies Retail Solutions Inc All rights reserved Document Part 026 4158 Rev 1 11 JAN 2017 Page 5 of 5 Technical Data Housing Self extinguishing ABS Mounting Panel mounting or wall mounting Frontal IP Protection IP54 without UR NTC sensor UL Type 1 enclosure Rear IP Protection IP20 Pollution Degree 2 Impulse Voltage Overvoltage category II Connections Type Panel version Pitch 5mm...

Reviews: