iTrust Adapt UPS 20kVA User Manual
28
Chapter 3 Operation And Display Panel
Menu
Item
Explanation
Settings
Display contrast
Adjust the LCD contrast
Date format set
YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be
selected.
Date & time
Set the date and time
Comm1 baud rate
Set the communication baud rate of the USB port
Comm2 baud rate
For internal communication only, can not be set
Comm3 baud rate
Set the communication baud rate of the SNMP card port
Communication address
This setting is suitable for RS485 communication
Communication mode
Set the communication mode
Callback times
If the communication mode of the SNMP card port is Modem, you can
set alarm callback times here
Phone No.1
If the communication mode of the SNMP card port is Modem, you can
set phone No.1 here
Phone No.2
If the communication mode of the SNMP card port is Modem, you can
set phone No.2 here
Phone No.3
If the communication mode of the SNMP card port is Modem, you can
set phone No.3 here
Command password
You can change the command password. Default
: ‘123456’
Single Group Batt Cap
Battery capacity
Battery cells Number
Set the battery cell. The setting options include: 30-cell, 32-cell,
34-cell, 36-cell, 38-cell, 40-cell
Equalize Charge
Allowed
Enabled or disenabled
Temp Compensation
Enabled or disabled
Temp Sensor Position
Set the position of the temperature sensor
. ‘Remote’ only
Shared Battery
Set each single in parallel system to share the battery group or not
System Configuration
Set the single/parallel
Parallel Requisite Units
Set the parallel number
Parallel Redundant
units
Set the redudant number
ECO Mode
ECO function enabled
Output Frequency Level
Set the output frequency
Output Voltage Level
Set the output voltage system
LBS Function
LBS function enabled
3-in 3-out/3-in 3-out
Set the output system: 3-in 3-out/3-in 3-out
This setting can only be carried out after the EPO operation. After the
setting, you must power off the system, and confirm that the system
actual connection mode complies with the setting. Power on again,
and the setting can come into force
Command (start, stop
battery, system test or
frocing boost charge)
Battery maintenance
test
The battery maintenance test will lead to the battery being partly
discharged, for rough assessment of the battery capacity. The load
must range from 20% ~ 100%
Battery capacity test
The battery capacity test will lead to the battery being completely
discharged, for accurate assessment of the battery capacity. The load
must range from 20% ~ 100%
System test
For UPS self-test. The user actives this function, 5 seconds later, a
pop window will appear to show the result of this test
Stop testing
Manually stop the test, including maintenance test, capacity test and
system test
Forcing charge
Manually conduct the forcing charge for battery
Stop forcing charge
Manually stop the forcing boost charge for battery
Version
Monitor Version
Provide the monitor software version
Rectifier Version
Provide the rectifier software version
Inverter Version
Provide the inverter software version
Keypad window
The function of menu buttons (F1 ~ F4 and HELP) is shown in icon mode for the current display screen.