Installation
Avtron Model LPH400 • Resistive Load Bank
Part Number LPH400D30693-1
3-5
LOAD CONNECTION
Connect a 240/480 volt, 3-phase source to the three fused bars labeled A, B and C, located in the
customer connection access box. Cables to the Load Bank should be sized to handle the
maximum rated load according to the National Electric Code. Verify load cables, lugs, and
mounting hardware have sufficient arc over clearance to sheet metal and cover when closed. The
current can be determined by the following formula:
Line Current =
kW
×
577
VOLTAGE (Line to Line)
*************************************************************
W A R N I N G
"B" Bus and any attached wiring are electrically hot when
operating Load Bank in single phase.
*************************************************************