Installation
Avtron Model LPH400 • Resistive Load Bank
Part Number LPH400D30693-1
3-6
GROUNDING
A permanent ground should be connected to the Load Bank enclosure either by a grounded
conduit or with a separate ground wire to prevent a potential above ground on the enclosure. No
internal ground connections are made to any terminal on the Load Bank.
The ground conductor should be run with the load power conductors to provide the lowest
impedance fault path. The ground stud must be connected to both the generator frame and a
good earth ground. The ground conductor should be sized for National Electric Code Table
250.122 if not superseded by local codes.
*************************************************************
W A R N I N G
Do not operate the Load Bank with any panel or screen removed.
This may expose the operator to dangerous high voltage and the
rotating fan blade, as well as disrupting the airflow.
Keep the hinged cover on connection access box closed and
latched.
*************************************************************
STORAGE
The Load Bank should be covered to limit long term effect of moisture and to reduce the
accumulation of dust and dirt. The unit should be stored in a dry, enclosed area. An optional
waterproof vinyl cover is available for the Load Bank; however, even with this cover, the Load
Bank should not be stored outdoors permanently.