background image

 

September 2015

Programming Instructions

TEC2-RS485-1001 Rev. 1

2

Section 1: TEC2 CCM Programming Instructions

TEC2 CCM Programming Instructions

Figure 2 

RS485 Adapter Box Connection 

3. 

Connect RS485 cable to STC pins 36 and 38. See Figure 3.  

Figure 3 

STC Pins 36 and 38

4. 

Set all switches on the RS485 Adapter box to ON. See Figure 4.

Summary of Contents for BETTIS TEC2 CCM

Page 1: ...Programming Instructions TEC2 RS485 1001 Rev 1 September 2015 TEC2 CCM Programming Instructions Using RS 485 UART Probe and STC Pins 36 and 38 ...

Page 2: ......

Page 3: ...e of Contents September 2015 Programming Instructions TEC2 RS485 1001 Rev 1 Table of Contents Table of Contents Section 1 TEC2 CCM Programming Instructions 1 1 Using RS 485 UART Probe and STC Pins 36 and 38 1 ...

Page 4: ...amming Instructions Section 1 TEC2 CCM Programming Instructions 1 1 Using RS 485 UART Probe and STC Pins 36 and 38 Figure 1 RS485 Setup 1 Connect USB cable to the RS485 Adapter and plug the other end of the cable into the USB port on the computer See Figure 1 2 Connect a two lead cable to the Phoenix connector See Figure 2 ...

Page 5: ... Section 1 TEC2 CCM Programming Instructions TEC2 CCM Programming Instructions Figure 2 RS485 Adapter Box Connection 3 Connect RS485 cable to STC pins 36 and 38 See Figure 3 Figure 3 STC Pins 36 and 38 4 Set all switches on the RS485 Adapter box to ON See Figure 4 ...

Page 6: ...ions TEC2 RS485 1001 Rev 1 September 2015 3 Section 1 TEC2 CCM Programming Instructions TEC2 CCM Programming Instructions Figure 4 Adapter Switch Settings 5 Go to Windows Control Panel and open device manager See Figure 5 ...

Page 7: ...001 Rev 1 4 Section 1 TEC2 CCM Programming Instructions TEC2 CCM Programming Instructions Figure 5 Windows Control Panel 6 Determine the RS485 Adapter box Com Port Number See Figure 6 Figure 6 Com Port Number 7 Open the TEC Flash exe program See Figure 7 ...

Page 8: ...ramming Instructions TEC2 CCM Programming Instructions Figure 7 TEC Flash exe Icon 8 Select the correct Comm port and then select Open See Figure 8 Figure 8 Open Comm Port 9 Enter the Modbus Address Click on Discover Select Check box for the Actuator then click on the CCM Tab See Figure 9 ...

Page 9: ... Figure 9 TEC Flash Program Discover Tab 10 On the CCM tab click Read Version button on Step 1 Then Click Read CRC on Step 2 Then click Open File on Step 3 See Figure 10 Figure 10 Perform Steps 1 and 2 then click Open File 11 Navigate to the directory that holds the BIN file you want to download Select that file and click open See Figure 11 ...

Page 10: ...red is the CRC in the code Calc is the CRC that TEC Flash calculated for the code on the board In the Step 3 box the Stored is the CRC for the new file that is stored in the new BIN file itself Calc is the value of the CRC that the TEC Flash exe program calculated for the BIN file you selected to download The Btldr Bootloader and App the Target executable file See Figure 12 Figure 12 Screen Showin...

Page 11: ... TEC2 CCM Programming Instructions 13 After the bootloader has started you should see Firmware Upgrade in Progress on the LDM See Figure 13 You should see that Step 4 Start Bootloader now shows Complete in Green and that Step 5 is now enabled to Upgrade Application See Figure 14 Figure 13 Bootloader Running ...

Page 12: ...hould now see the Step 5 In Progress and the green download status bar See Figure 15 Figure 15 Download in Progress Takes 5 to 6 minutes to finish with wired connection 15 When the Download has completed you can now perform Steps 7 8 and 9 Step 9 restarts the actuator code and should now be running the new code you just downloaded See Figures 16 and 17 Figure 16 Start Application ...

Page 13: ...EC2 RS485 1001 Rev 1 10 Section 1 TEC2 CCM Programming Instructions TEC2 CCM Programming Instructions Figure 17 Application Started 16 The code in the Actuator should now be running and the version should be the new version that you downloaded ...

Page 14: ......

Page 15: ...ongmeadow Business Estate East P O Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T 27 11 451 3700 EUROPE Holland Fasor 6 Székesfehérvár 8000 Hungary T 36 22 53 09 50 Strada Biffi 165 29017 Fiorenzuola d Arda PC Italy T 39 0523 944 411 www emerson com bettis 2018 Emerson All rights reserved The Emerson logo is a trademark and service mark of Emerson Electric Co BettisTM is a mark ...

Reviews: