Site Preparation
Centellis 2000 Shelf Release 3.0 Installation and Use (6806800L99F
)
44
2.3.1
Environmental Requirements
To ensure proper function of the system, make sure that the environment in which the system
is to be used fulfills the environmental requirements.
The environmental values must be tested and proven in the planned system configuration,
that is, the delivered system and other third-party products you want to integrate.
The following table lists the environmental requirements.
z
Operating temperatures refer to the temperature of the air circulating at the air intake of
the system and not to component temperatures.
z
Some of the climatic values may exceed the specification of some system components
(for example, hard disks). As Emerson cannot guarantee the functionality of third party
products that are handled or operated out of their specifications, the environmental
conditions may be limited to the specifications of these components.
Table 2-1 Environmental Conditions
Feature
Operating
Non-Operating (packed state)
Temperature
+5 ºC (41 °F) to +40 ºC (104 °F)
(normal operation) according to NEBS
standard GR-63-CORE
-5 °C (23 °F) to +55 °C (131 °F)
(exceptional operation) according to NEBS
standard GR-63-CORE
-40 °C (-40 °F) to +70 °C (158 °F)
Temp. change
+/-0.5 °C/min according to NEBS standard
GR-63-CORE
+/-0.5 °C/min
Relative
humidity
5% to 90% non-condensing
according to Emerson-internal
environmental requirements
5% to 95% non-condensing
according to Emerson-internal
environmental requirements
Vibration
(tested in
target
platform)
0.1 g from 5 to 100 Hz and back to 5 Hz at
a rate of 0.1 octave/minute
5-20 Hz at 0.01 g
2
/Hz
20-200 Hz at -3.0 dB/octave
Random 5-20 Hz at 1m
2
/Sec
3
Random 20-200 Hz at -3 dB/octave
Shock
Half-sine, 11 mSec, 30 m/Sec
2
Blade level packaging
Half-sine, 6 mSec at 180 m/Sec
2
Summary of Contents for Centellis 2000 Shelf Release 3.0
Page 8: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 8 ...
Page 10: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 10 List of Tables ...
Page 12: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 12 List of Figures ...
Page 40: ...System Overview Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 40 ...
Page 52: ...Site Preparation Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 52 ...
Page 87: ...FRU Installation Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 87 ...
Page 108: ...Cooling Subsystem Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 108 ...
Page 116: ...Power Subsystem Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 116 ...
Page 146: ...Redundancy Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 146 ...
Page 154: ...Software Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 154 ...
Page 158: ...Troubleshooting Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 158 ...
Page 174: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F Safety Notes 174 ...
Page 188: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F Sicherheitshinweise 188 ...
Page 192: ...Index Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 192 ...
Page 193: ......