102
ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 11: SERIAL LINK - DRIVE CHARACTERISTICS - MISCELLANEOUS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: Quick setup menu access
Adjustment range : 0 to 2
Factory setting
: 0
This parameter determines the access level in menu 0, but
only when the drive keypad is used.
The locking procedure using a security code is described in
section 4.3.6 of the installation and commissioning manual
ref. 3840.
11.44
LCD
display
LED
display
Access level
0
Level 1
L1
Access to parameters
01
to
10
1
Level 2
L2
Access to parameters
01
to
80
2
Read only
Loc
All parameters can be
read, but none can be
modified, unless a code
the same as parameter
11.30
is entered at the
time of accessing the
parameter.
11.44
: Motor parameter select
Adjustment range : 0 or 1
Factory setting
: 0
This parameter is used to select the set of parameters corresponding to the characteristics of motor 2.
WARNING:
• Switching from one set of motor parameters to the other is performed with the drive disabled.
• When the parameter set for motor 2 is selected, all punctuation marks on the display are lit except for the comma.
11.45
= 0 (Motor 1) (Mot1)
11.45
= 1 (Motor 2) (Mot2)
Description
1.06
21.01
Maximum reference clamp
1.07
21.02
Minimum reference clamp
1.14
21.03
Reference selector
2.11
21.04
Acceleration ramp
2.21
21.05
Deceleration ramp
5.06
21.06
Rated frequency
5.07
21.07
Rated current
5.08
21.08
Rated speed
5.09
21.09
Rated voltage
5.10
21.10
Rated power factor (cos
ϕ
)
5.11
21.11
Number of motor poles
5.17
21.12
Stator resistance
5.23
21.13
Voltage offset
5.24
21.14
Transient inductance
-
21.15
Motor 2 parameters active
5.25
21.24
Stator inductance (Ls)
5.33
21.30
Motor volts per 1000 rpm (Ke)
5.51
21.51
q axis inductance
11.45