MENU 12: THRESHOLD DETECTORS, VARIABLE SELECTORS AND BRAKE CONTROL FUNCTION
CONTROL TECHNIQUES
3854 en - 03.2008 / b
14.3 - Explanation of parameters in
menu 12
: Comparator 1 output
: Comparator 2 output
: Comparator 3 output
: Comparator 4 output
Adjustment range : 0 or 1
0 (Disabled) (OFF): The input variable is less than or equal
to the comparator threshold.
1 (Enabled) (On):The input variable is greater than the
comparator threshold.
: Comparator 1 source
: Comparator 2 source
: Comparator 3 source
: Comparator 4 source
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters define the variable which is to be
compared to the configured threshold.
The absolute value of the variable is taken into account. Only
non-bit parameters can be programmed as the source.
If an unsuitable parameter is programmed, the input value is
taken to equal 0.
: Comparator 1 threshold
: Comparator 2 threshold
: Comparator 3 threshold
: Comparator 4 threshold
Adjustment range : 0 to 100.0%
Factory setting
: 0
These parameters are used to set the comparator trip
threshold.
The threshold is expressed as a percentage of the maximum
value of the compared variable.
: Comparator 1 hysteresis
: Comparator 2 hysteresis
: Comparator 3 hysteresis
: Comparator 4 hysteresis
Adjustment range : 0 to 25.0%
Factory setting
: 0
These parameters define the window within which the
comparator output will not change state.
The output will change to 1 when the variable reaches the
threshold value + (hysteresis /2).
The output will change to 0 when the variable drops below the
threshold value - (hysteresis /2).
The hysteresis is expressed as a percentage of the maximum
value of the compared variable.
: Comparator 1 output invert
: Comparator 2 output invert
: Comparator 3 output invert
: Comparator 4 output invert
Adjustment range : 0 or 1
Factory setting
: 0
These parameters are used to invert the comparator output.
0 (Disabled) (OFF): Output not inverted.
1 (Enabled) (On): Output inverted.
: Comparator 1 output destination
: Comparator 2 output destination
: Comparator 3 output destination
: Comparator 4 output destination
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters define the internal parameter which will be
assigned by the comparator output.
Only bit type parameters can be programmed.
If an unsuitable parameter is programmed, the output is not
sent to any address.
: Function 1 variable 1 source
: Function 2 variable 1 source
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters define the source parameter for variable 1
to be processed.
Only "numerical" parameters (read-only) can be assigned.
If an unsuitable parameter is selected, the value of the
variable will be 0.