73
ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 7: ASSIGNMENT OF ANALOG INPUTS AND OUTPUTS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: ADI1 min. threshold
Adjustment range : 0 to 1.00
Factory setting
: 0
This parameter is a multiplication coefficient applied to the
maximum value of the ADI1 destination parameter. For a 0
value of the analog input, it is used to obtain a value different
from the minimum value of the destination parameter.
Value 0 = (
7.58
x destination parameter max. value) +
destination parameter min. value.
Example: ADI1 is assigned to a parameter with an adjustment
range of 0 - 30000. If
7.58
= 0.01, 0 - 100% on ADI1
corresponds to 300 - 30000.
: ADI2 min. threshold
Adjustment range : 0 to 1.00
Factory setting
: 0
This parameter is a multiplication coefficient applied to the
maximum value of the ADI2 destination parameter. For a 0
value of the analog input, it is used to obtain a value different
from the minimum value of the destination parameter.
Value 0 = (
7.59
x destination parameter max. value) +
destination parameter min. value.
Example: ADI2 is assigned to a parameter with an adjustment
range of 0 - 30000. If
7.59
= 0.01, 0 - 100% on ADI2
corresponds to 300 - 30000.
: ADIO3 min. threshold
Adjustment range : 0 to 1.00
Factory setting
: 0
This parameter is a multiplication coefficient applied to the
maximum value of the ADIO3 destination parameter. For a 0
value of the analog input, it is used to obtain a value different
from the minimum value of the destination parameter.
Value 0 = (
7.60
x destination parameter max. value) +
destination parameter min. value.
Example: ADIO3 is assigned to a parameter with an
adjustment range of 0 - 30000. If
7.60
= 0.01, 0 - 100% on
ADIO3 corresponds to 300 - 30000.
Note: This parameter only applies when ADIO3 is configured
as an input.
: Scaling block min. threshold
Adjustment range : 0 to 1.00
Factory setting
: 0
This parameter is a multiplication coefficient applied to the
maximum value of the block's destination parameter. For a
zero value of the source parameter, it is used to obtain the
minimum value of the destination parameter.
Value 0 = (
7.61
x destination parameter max. value) +
destination parameter min. value.
Example: The potentiometer input is assigned to a parameter
with an adjustment range of 0 - 30000. If
7.61
= 0.01,
0 - 100% on the potentiometer input corresponds to
300 - 30000.
: Block scaling
Adjustment range : 0 to 2.50
Factory setting
: 1.00
This parameter is used, if necessary, to scale the
potentiometer input. However, this rarely proves necessary
since the maximum level of the input automatically
corresponds to the maximum value of the destination
parameter.
:Scaling block invert
Adjustment range : 0 or 1
Factory setting
: 0
This parameter is used to invert the polarity of the
potentiometer input.
0 (Disabled) (OFF): Input not inverted.
1 (Enabled) (On): Input inverted.
: Scaling block destination
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
Used to define the destination for the reference from the
potentiometer. With the local control option, the potentiometer
input destination is assigned to parameter
1.36
(analog
reference 1). In this case,
1.36
is unassigned from
7.10
(analog input 1). The destination can then be modified at any
time by the user. In this case,
1.36
can then be assigned to
another analog input.
: PTC status
Adjustment range : 0 or 1
Indicates the status of the PTC sensor.
0 (NotTRIGGERED) (OFF): PTC not tripped.
1 (TRIGGERED) (On): PTC tripped.
: Internal braking resistor temperature
Adjustment range : 0 to 200.0 °C
Indicates the temperature measured on the braking resistor.
The drives trips when the temperature reaches 110 °C, and
can be reset when the temperature falls below 100 °C again.
: Local control potentiometer input
Adjustment range : 0 to 100.0%
Used to read the value of the potentiometer input coming from
the local controls.
: Scaling block source
Adjustment range :
0.00
to
21.51
Factory setting
:
7.67
This parameter is used to select the source to be scaled.
If an unsuitable parameter is selected, the input value will be
0.
: Scaling block read
Adjustment range : ± 32000
Used to read the output value.
7.58
7.59
7.60
7.61
7.62
7.63
7.64
7.65
7.66
7.67
7.68
7.69