EN Drive Installation Manual
Figure 4:
AC Filter and Cable Connections for EN Drives
Environmental Considerations
If the product will be subjected to atmospheric contaminants such as moisture, oils,
conductive dust, chemical contaminants and metallic particles, you must mount it vertically
in a metal NEMA type 12 enclosure.
If the ambient temperature inside the enclosure will exceed 40° C (104° F), you must consider
forced air cooling.
Note
It is necessary to maintain the drive surround air ambient temperature at 40° C (104° F)
[50°C (122ºF) with derating of 3% per degree above 40° C].
The amount of cooling depends on the size of the enclosure, the thermal transfer of the
enclosure to the ambient air and the amount of power being dissipated inside the enclosure.
Consult your enclosure manufacturer for assistance with determining cooling requirements.
NEMA Enclosure
This wail must have good
continuity to enclosure ground.
Through wall shield grommets
External Encoder
CMDS or CMMS Cable
CFOS
Cable
CFOS
Cable
CMDS or CMMS Cable
CFCO Cable
Customer supplied
terminal strip
(Connect Shield Through)
The CFCS cable can
be cut and connected
through a terminal strip
instead of using a CFOS
and a CFCO cable.
Drive
Bonded to mounting plate
and enclosure wall
AC In
3-phase
filter
EMC testing was done
with surface paint
removed from the
mounting panel area
for drive contact.
Motor
Note:
Note: