Operating instructions
cod. 1592
cod. 1592
cod. 1592
cod. 1592017400
017400
017400
017400
1592017400 XLH260 GB r1.0 15.04.2005.doc
XLH260
15/15
doA
0
Pr2
Open door alarm delay
0 ÷ 250 min ( 250 = nu )
ot
0.0
Pr1
Thermostat probe calibration
-12.0 ÷ 12.0
oE
0.0
Pr2
Evaporator probe calibration
-12.0 ÷ 12.0
o3
0.0
Pr1
Humidity probe calibration
-10 ÷ 10
P2P
YES
Pr2
Evaporator probe presence
no
= absent /
YES
= present
P3P
YES
Pr2
Humidity probe presence
no
= absent /
YES
= present
Lci
0
Pr2
Readout with 4 mA
-999 ÷ 999
uci
100
Pr2
Readout with 20 mA
-999 ÷ 999
i1P
cL
Pr2
Configurable digital input polarity
cL =open / oP = close
i2P
cL
Pr2
Door switch digital input polarity
cL =open / oP = close
i1F
EAL
Pr2
Digital input configuration
dor / PAL / EAL / bAL / Ht
odc
FAn
Pr2
Outputs status when open door
on / Fan / oFF
rrd
YES
Pr2
Outputs restarting after doA alarm
no = no / YES = yes
did
5
Pr2
Digital input alarm delay
0÷255 min.
oA1
Lig
Pr2
Light relay configuration:
ALr
= alarm;
dEH
= dehumidifier;
onF
= on/off;
Lig
= light,
ESt, dEF not select
Adr
1
Pr2
Serial address
0÷247 num
Ptb
-
Pr2
Parameter table
- - -
rEL
1.0
Pr2
Software release
- - -
Prd
--
Pr2
Probes display
Pb1÷Pb3
Pr2
321
Pr1
Access to the protected parameter list
- - -