Electrical connection
4.1
General recommendations
The compressor terminal box has a wiring diagram on the inside of its cover. Before connecting
the compressor, ensure the supply voltage, the phases and the frequency match the nameplate
data.
When the compressor is shipped the motor protector is mounted in the terminal box. The
thermistors are factory connected. The power supply and the control circuit must be wired
according to the wiring diagram (see wiring diagram on the inside of the terminal box lid).
Figure 12: Terminal box preparation for cable gland fitting - Note position of screwdriver!
Position at
terminal box
Diameter of hole at
terminal box (mm)
Cable bushing
metric
Outside
diameter (mm)
1
20.6
M20 x 1.5
20
2
32.5
M32 x 1.5
32
3
50.5
M50 x 1.5
50
4
63.5
M63 x 1.5
63
Table 2: Characteristics of the holes for cable bushings
Figure 13: Position of the holes for cable bushings (top view of a 6-cylinder compressor)
The protection class of each terminal box according to IEC 60529 is given in
Table 3
hereunder:
Old models
Present models
Class
Option
DK, DL, D2D, D2S
K, L, 2D
IP54
-
D3D, D3S
3D
IP54
IP56
D4D, D4S
IP54
IP56
D6D, D6S, D6T
6T
IP54
IP56
D8D, D8S
8D
IP54
IP56
Table 3: Protection class of terminal box according to IEC 60529
Cable glands can influence the protection class. Factory-fitted cable glands reduce the
protection class to IP41.
4.2
Electrical installation
4.2.1 Single-phase motors
– Code C
Compressors up to model DKSL-15X are available with single-phase motors. They have one
main and one auxiliary winding. A single-phase equipment consisting of a start and run capacitor