Current Status
1
0
1
Trip with Auto Reset (2XX)
200: High Discharge Line Temperature
202: Locked Rotor
203: Missing Phase
205: Compressor Low Voltage
208: Voltage Imbalance
212: Motor Overheat
Lockout with Manual Reset (3XX)
300:High Discharge Temperature
302:Locked Rotor
303:Missing Phase
304:Phase Loss
307:Insufficient Oil Pressure
311:Control Module Failure
312:Compressor Low Voltage
011C
DIP-Switch_1
1
0
1
Communication Board DIP Switch:
BIT15 - DS15
BIT14 - DS14
……………
BIT1 - DS1
BIT0 - DS0 1 = ON 0 = OFF
0123
Input Status
1
0
1
BIT0 - Demand Status
1 = Present
0
1
BIT1 - Compressor Running
BIT2 - Injection Present
BIT3 - Top Cap Thermistor installed
BIT4 - 250 DTC valve thermistor installed
BIT5 - TRUE if solenoid is open
1=TRUE 0=FALSE
0
1
BIT6 - Operating Voltage
1 = 230V, 0 = 110V
1
2
BIT7 - Line Frequency
1 = 50Hz 2 = 60Hz
0126
Output Status1
1
0
1
BIT3 - CrankCase Heater Status
0 = Open 1 = Closed
0127
Output Status2
0
1
BIT14
–Previous Reset Status
0 = Hard reset 1 = Soft reset
0
1
BIT13 -Oil Pressure Status
BIT12 -HPCO Status
BIT11 -LPCO /Suction pressure Status
1 = Normal 0 = Trip
0
1
BIT10
–PTC3 Status
BIT9 -PTC2 Status
BIT8 -PTC1 Status
0 = Normal 1= Trip
0
1
BIT7 - Spare Input -1 Status
BIT6 - Spare Input -2 Status
BIT4 -StandAlone_Unloader_2 Command
Status
BIT3 -StandAlone_Unloader_1 Command
Status
BIT2
– Standalone Demand Status
0 = Not active 1 = Active
0
1
BIT5- Wake up pushbutton status
0 = Not pressed 1 = Pressed
0
1
BIT1
– Unloader2 Triac Short Circuit
Protection Input Status
BIT0 - Unloader1 Triac Short Circuit
Protection Input Status
0 = Normal
1 = short circuit condition has happened
0129
Discharge Temperature Value
1
-70.0
585.35
°F
(Discharge temp sensor value/100)-70
012B
Compressor R Phase Voltage
1
0
655,35
V
1/100 (R Phase Compressor Voltage/100)
012C
Compressor Y Phase Voltage
1
0
655,35
V
1/100 (Y Phase Compressor Voltage/100)
012D
Compressor B Phase Voltage
1
0
655,35
V
1/100 (B Phase Compressor Voltage/100)