D7.8.6/1112-0815/E
5/18
3.2
Modbus with 12 DIP-switch
– New version
Figure 2: View of the circuit board and label for 10 DIP-switch Modbus
3.3
DIP-Switch functions
DIP-switch function
Factory
setting
DIP-switch position
10 DIP-
switch
12 DIP-
switch
Node address for communication
On
1
1
Node address for communication
Off
2 to 5
2 to 6
Communications Baud rate
Off: 19200 Baud
On: 9600 Baud
Off
7
7
Off: No parity
On: Even parity
Off
8
8
Off: Stand-alone mode
On: Network mode
Off
9
9
On: DLT enabled
Off: DLT disabled
On
10
10
Self-test function for oil functionality
TBD
---
11
On: VFD application
Off: Non VFD application
Off
6
12
Table 2: CoreSense Diagnostics DIP-switch setting
NOTE:
The following chapters are based on the operation of the present Modbus (12 DIP-switch). For the
other Modbus type, please refer to Chapters 3.1 and 3.3 about the 10 DIP-switch model.