10
C6.1.11/0718-0619/E
If a system does not require cooling capacity and the ambient temperature around the unit is high,
the pressure in the flashtank section will increase. When reaching a critical pressure limit defined by
parameter
GC78
(factory-set at 40 bar) inside the flashtank during compressor stop, the compressor
will start and perform a short pumpdown cycle to reduce the pressure level in the flashtank area.
2.7.7 Housing
Copeland EazyCool CO
2
refrigeration units have a new, unique design. They are equipped with an
electrical cabinet located above the compressor chamber with a hinged cover for easy and service-
friendly access. The electrical cabinet and the compressor area are accessible independently. The
fan has vertical air flow and is protected by a safety grid. The gas cooler, liquid receiver and
connected parts are freely accessible by the service technician.
Figure 10: Overview of the unit housing
Figure 11: Position of the connections