28
C6.1.11/0718-0619/E
Press the
ALARM
key to enter the "Alarm" menu:
Figure 36: iPro "Alarm" key
The header of the corresponding menu will be flashing. Four alarm menus are available from the
display:
▪
Compressor alarms Circuit 1
▪
Fan alarms Circuit 1
▪
Alarms Circuit 1
▪
Generic alarms
An additional alarm menu is available from the iPro internal webpage.
1)
Use the
UP
and
DOWN
keys to select the desired alarm section
2)
Press
ENTER
to confirm and access the alarm sub-menu
Figure 37: Active alarms screen
The alarm menu will display the active alarm in the following format:
▪
Column 1: Alarm code
▪
Column 2: Alarm description
Several alarms are pre-programmed in the unit. The configuration can easily be adjusted to
the user’s
needs. The factory settings only consider a general compressor alarm (Parameter
AL09
"Relay for
temperature/pressure compressors alarms"), and a general fan alarm, both connected to "
ALR
".
Alarm
Factory setting
Description
Wiring
diagram
Function
ALR1
ALR1
X4: 80 / 76
ALR1
R4
ALR2
ALR2
X4: 80 / 77
ALR2
R5
ALR3
ALR
X4: 80 / 78
ALR
R6
ALR4
Reserved
X4: 80 / 79
ALR4
R7
ALR5
Reserved
X4: 80 / 81
ALR5
R8
PFC
Potential free contact (source 24VAC (69))
Operation mode
X4: 69 / 47
PFC
Potential free contact (source 24VAC (69))
Not used
X4: 69 / 48
PFC
Potential free contact (source 24VAC (69))
Not used
X4: 69 / 49
Table 17: Alarm overview
Compressor alarm:
The activation of the relay for temperature/pressure compressor alarms can be
set in the "Compressor alarms" menu.
Parameter
AL10
allows for an additional alarm for "Running hours for compressor maintenance"
(factory setting >> 0 = not used). To activate the maintenance alarm change
AL10
from "nu - not
used" to
ALR1
or
ALR2
.