50
C6.1.11/0718-0619/E
Appendix 1: Alarm menu iPro IPR215D controller
Alarms Circuit 1
Code
Name on
Visograph
Description
Cause
Action
Reset
LP1
EOL1
Low-pressure-
switch alarm in
Circuit 1
Low-pressure switch Input 1
(the input is configured as
DIC = 51 Low-pressure Circuit 1)
▪
All compressors in Circuit
1 are turned off
▪
Fans follow SL16
Automatically
if the number of
activations is less than AL12 in the AL13
time when the input is disabled.
-
Compressors restart working
according to the working algorithm.
Manually
if AL12 activations happened
in the AL13 time.
When the input is disabled:
-
Turn the device off and on again or
reset the alarm manually from the
Visograph.
-
Compressors restart working
according to the working algorithm.
HP1
EOH1
High-pressure
switch alarm in
Circuit 1
High-pressure switch Input 1
(the input is configured as
DIC = 50 High-pressure Circuit 1)
▪
All compressors in Circuit
1 are turned off
▪
All fans in Circuit 1 are
turned on. Inverter fan /
linear inverter for fan at
maximum speed
Automatically
if the number of
activations is less than AL29 in the AL30
time when the input is disabled.
-
Compressors and fans restart
working according to the working
algorithm.
Manually
if AL29 activations happened
in the AL30 time.
When the input is disabled:
-
Turn the device off and on again or
reset the alarm manually from the
Visograph.
-
Compressors and fans restart
working according to the working
algorithm.