2.7.3 Liquid receiver
The liquid receiver (24.9 litres for the whole range of units) is installed below the condenser / gas
cooler. It is equipped with a shut-off valve on the outlet and a safety group (2 pressure relief valves
90 bar, connected to a switch-over valve).
There are 2 sight glasses in the shell of the liquid receiver to check the refrigerant level.
2.7.4 Fan
The condenser of the Copeland EazyCool CO
2
refrigeration unit is equipped with an EC fan.
Figure 9: Fan design
Fan
Power
input
[W]
Maximal
current
[A]
Air flow
[m³/h]
Unit
Description
OME-4MTL-05X
FN071-6IQ.BD.V7P3
280
1.4 - 1.0
7100
OME-4MTL-07X
FN071-ZIQ.DG.V7P3
660
3.4 - 2.4
11950
OME-4MTL-09X
FN071-ZIQ.DG.V7P3
660
3.4 - 2.4
11950
Table 4: Fan specifications
Technical data
Supply frequency
[Hz]
50/60 Hz
Supply voltage
[V]
200-277
Min to max ambient temperature
[°C]
-35 to +60
ErP 2015
[-]
Yes
IP class
[-]
IP54
Fan motor type
[-]
EC
Fan blades
[-]
Plastic
Table 5: Fan technical data
2.7.5 Condenser / gas cooler regulation valve (HPV)
The high-pressure regulation valve is installed between the condenser / gas cooler and the liquid
receiver. It regulates the high pressure for optimum COP in transcritical operation.
The driver for the stepper motor valve is installed in the electrical cabinet.
The driver for the HPV is an XEV20D. It gets a signal from the iPro unit controller
– see chapter 2.8
2.7.6 Flashgas bypass valve (BPV)
The flashgas bypass valve is installed between the flashtank and the suction line to the compressor.
Without the flashgas bypass valve there is a risk of unacceptably high pressure in the flashtank in
case the ambient temperature exceeds 35°C. The flashgas bypass valve is aimed at keeping the
flashtank pressure below a set level defined by parameter
GC20
(factory-set at 35 bar) at all times.