2.9.8 How to check the values of digital inputs
1)
Enter the "Service" menu
2)
Use the
UP
and
DOWN
keys to select the "Digital inputs" sub-menu
3)
Press
ENTER
Figure 26: iPro "Digital inputs" screen
Digital
input
Factory setting
Description
Wiring
diagram
Function
DIC1
o63 - Inverter suction
1 safety
VF drive failure
NO >> Normally open, closed if failure
X1: 40
DI1
DIC2
0 - Not used
HP switch
NC >> Normally closed, open if high
pressure
X1: 41
DI2
DIC3
0 - Not used
Oil alarm
NC >> Normally closed, open if oil alarm
X1: 42
DI3
DIC4
0 - Not used
Motor winding temperature alarm (KRIWAN)
NC >> Normally closed, open if motor
temperature alarm
X1: 43
DI4
DIC5
0 - Not used
VF drive under power
NC >> Normally closed, open if drive is not
powered
X1: 44
DI5
DIC6
0 - Not used
Fan alarm
Closed after power on, open if fan alarm
X1:
DI6
DIC7
0 - Not used
Fan alarm 2
nd
input
Closed after power on, open if fan alarm
X1: 46
DI7
DIC8
0 - Not used
Operation mode
Potential free contact controlled by user
X1: 47
DI8
DIC9
0 - Not used
X1: 48
DI9
DIC10
0 - Not used
X1: 49
DI10
DIC11
0 - Not used
DI11
DIC12
o60 - Safety inverter
condenser - Circuit 1
DI12
DIC13
0 - Not used
DI13
DIC14
0 - Not used
DI14
DIC15
o57 - Oil frequency
compressor suction -
Circuit 1
DI15
DIC16
0 - Not used
DI16
DIC17
o58 - Safety
frequency compressor
suction - Circuit 1
DI17
DIC18
o59 - Thermal safety
of frequency
compressor
DI18
DIC19
o74 - External alarm 1
DI19
DIC20
C95 - Operating mode
2
DI20
Table 13: Digital inputs overview