NOTE: In order to meet the requirements of the Ecodesign Directive 2009/125/EC with regard
to efficient system operation, ensure the heat exchangers remain clean at all times.
5.4 Electrical connections
WARNING
Isolating switch "On"! Danger of electric shock!
Turn off the main power
supply to de-energise the unit before undertaking any task on electrical
equipment.
All condensing units will generate some degree of vibration. Copeland EazyCool CO
2
refrigeration
units are no exception. Over time, due to these slight vibrations and to temperature fluctuations within
the unit housing, electrical terminations might become loose. The components most likely to be
affected are the main terminal strip and the compressor contactor. It is recommended to check the
main electrical terminations for tightness and to carry out a visual inspection of the low voltage
crimped terminals at least once every 6 months.
5.5 Routine leak testing
All joints inside the system should be leak-tested as part of a regular maintenance schedule.
NOTE: In order to meet the requirements of the Ecodesign Directive 2009/125/EC with regard
to efficient system operation, ensure the refrigerant and oil charges are sufficient.
5.6 Condenser fan & motor
A yearly inspection of these items is recommended. Fastenings can become loose; bearings may
wear out and fans may require cleaning of solid deposits that can cause rotational imbalance.
Motors come with lifelong lubrication bearings that do not require lubricating on a routine basis, but
just need to be checked for wear.
6
Certification & approval
▪
Copeland EazyCool CO
2
refrigeration units comply with the Low Voltage Directive
LVD 2014/35/EU. The applied harmonised standard is EN 60335 (Household and similar
electrical appliances
– Safety, Part 1: General Requirements and Part 2-89: Particular
requirements for commercial refrigerating appliances with an incorporated or remote refrigerant
condensing unit or compressor).
▪
The refrigeration units and their piping comply with the Pressure Equipment Directive
PED 2014/68/EU (Art.3 §3 - Sound Engineering Practice). The unit itself belongs to PED
Category III.
▪
The refrigeration units and their components as far as required are CE marked and thereby
establish conformity with the relevant directives.
▪
Conformity Declarations for components are available as far as required.
▪
The Manufacturer's Declaration of Incorporation has to be respected when incorporating these
products into a machine.
7
Dismantling & disposal
Removing oil and refrigerant:
▪
Do not disperse in the environment.
▪
Use the correct equipment and method of removal.
▪
Dispose of oil and refrigerant in compliance with national legislation
and regulations.
Dispose of compressor and/or unit in compliance with national legislation
and regulations.