2.3 Main product features
Copeland EazyCool refrigeration units are released for CO
2
(R744) refrigerant only. They are
available in one cabinet size and are always equipped with one fan.
The units are designed for medium temperature applications only. The inverter is calculated to drive
the compressor in subcritical and transcritical applications.
Refrigeration unit
Refrigerant
type
Displacement
@ 50 Hz [m
3
/h]
Cooling
capacity*
[kW]
Nominal
power
[kW]
Max.
current
[A]
Ps
high side
[bar]
Ps
low side
[bar]
OME-4MTL-05X
R744
4.6
8.72
11
19
120/90
90
OME-4MTL-07X
6.2
11.81
14
22
OME-4MTL-09X
7.4
14.65
16
27
* Cooling capacity declared at ambient temperature 32°C, evaporating temperature -10°C, suction temperature
0°C and compressor frequency 50 Hz
Table 1: CO
2
unit technical data
Refrigeration unit
Outer dimensions
length/width/height with
closed cover [mm]
Weight
[kg]
Liquid
receiver size
[litres]
OME-4MTL-05X
1579 / 954 / 1109
440
24.9
OME-4MTL-07X
450
OME-4MTL-09X
462
Table 2: CO
2
unit features
The figures hereafter show the overall physical dimensions of the CO
2
refrigeration units in
millimetres.
Figure 2: Dimensions of models OME-4MTL-05X, OME-4MTL-07X & OME-4MTL-09X
NOTE: When the electrical cabinet cover is open the total height is 1722 mm. This must be
taken into consideration when deciding on the unit location, to ensure easy access to the
electrical cabinet.