C6.1.6/0117-1017/E
51
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
E15
Lower suction pressure point for condenser
fan map 4 (for R404)
-1.5 bar to HP4; -21 PSI to HP4
1.3
N.V.
N.V.
N.V.
E16
High setpoint for condenser fan map 4 (for
R407C)
LT4 to 110°C
38
N.V.
N.V.
N.V.
E17
High suction pressure point for condenser fan
map 4 (for R404)
LP4 to 99.9 bar; LP4 to 999 PSI
5.4
N.V.
N.V.
N.V.
E18
Low setpoint for condenser fan map 5 (for
R407A)
-40°C to HT5
10
N.V.
N.V.
N.V.
E19
Low suction pressure point for condenser fan
map 5 (for R407A)
-1.5 bar to HP5; -21 PSI to HP5
2.5
N.V.
N.V.
N.V.
E20
High setpoint for condenser fan map 5 (for
R407A)
LT5 to 110°C
27
N.V.
N.V.
N.V.
E21
High suction pressure point for condenser fan
map 5 (for R407A)
LP5 to 99.9 bar; LP5 to 999 PSI
5.3
N.V.
N.V.
N.V.
E22
Low setpoint for condenser fan map 6 (for
R407F)
-40°C to HT6
10
N.V.
N.V.
N.V.
E23
Low suction pressure point for condenser fan
map 6 (for R407F)
-1.5 bar to HP6; -21 PSI to HP6
1.7
N.V.
N.V.
N.V.
E24
High setpoint for condenser fan map 6 (for
R407F)
LT6 to 110°C
38
N.V.
N.V.
N.V.
E25
High suction pressure point for condenser fan
map 6 (for R407F)
LP6 to 99.9 bar; LP6 to 999 PSI
6.3
N.V.
N.V.
N.V.
E26
Low setpoint for condenser fan map 7 (for
R448A)
-40°C to HT7
10
N.V.
N.V.
N.V.
E27
Low suction pressure point for condenser fan
map 7 (for R448A)
-1.5 bar to HP7; -21 PSI to HP7
3.3
N.V.
N.V.
N.V.
E28
High setpoint for condenser fan map 7 (for
R448A)
LT7 to 110°C
30
N.V.
N.V.
N.V.
E29
High suction pressure point for condenser fan
map 7 (for R448A)
LP7 to 99.9 bar; LP7 to 999 PSI
7.2
N.V.
N.V.
N.V.
E30
Low setpoint for condenser fan map 8 (for
R449A)
-40°C to HT8
10
N.V.
N.V.
N.V.
E31
Low suction pressure point for condenser fan
map 8 (for R449A)
-1.5 bar to HP8; -21 PSI to HP8
3.3
N.V.
N.V.
N.V.
E32
High setpoint for condenser fan map 8 (for
R449A)
LT8 to 110°C
30
N.V.
N.V.
N.V.
E33
High suction pressure point for condenser fan
map 8 (for R449A)
LP8 to 99.9 bar; LP8 to 999 PSI
7.2
N.V.
N.V.
N.V.
E34
Low setpoint for condenser fan map 9 (for
R410A)
-40°C to HT9
10
N.V.
N.V.
N.V.