C6.1.6/0117-1017/E
52
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
E35
Low suction pressure point for condenser fan
map 9 (for R410A)
-1.5 bar to HP9; -21 PSI to HP9
3.3
N.V.
N.V.
N.V.
E36
High setpoint for condenser fan map 9 (for
R410A)
LT9 to 110°C
30
N.V.
N.V.
N.V.
E37
High suction pressure point for condenser fan
map 9 (for R410A)
LP9 to 99.9 bar; LP9 to 999 PSI
7.2
N.V.
N.V.
N.V.
E38
Fan setpoint modulation enabling
No (0-NO) - Yes (1-YES)
NO
L2
L2
L2
E39
Condenser temperature setpoint when fan
setpoint modulation is disabled
-40°C to 110°C
27
L1
L1
L1
E40
Minimum condenser temperature setpoint
-40°C to 110°C
10
L2
L2
L2
E41
High ambient fan motor override enabled
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
E42
High ambient fan motor override differential
0.1°C to 25.5°C
5
L2
L2
L2
E43
High DLT fan motor override enabled
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
E44
High DLT fan motor override differential
-40°C to 180°C
120
L2
L2
L2
E45
Minimum fan motor speed
0 to 100%
40
N.V.
N.V.
N.V.
E46
Regulation band of variable fan
0.1°C to 25.5°C
10
L1
L1
L1
E47
Integration time for fan
0 to 999 sec
500
L2
L2
L2
E48
Fan full speed duration at fan start-up
0 to 255 sec
0
L2
L2
L2
E49
Fan minimum on time
0 to 255 sec
5
L2
L2
L2
E50
Fan minimum off time
0 to 255 sec
10
L2
L2
L2
E51
Fixed condenser fan setpoint
-40°C to 110°C
23
L2
L2
L2
E52
Fan 1 differential
0.1°C to 25.5°C
7
L2
L2
L2
E53
Fan 1 to fan 2 differential
0.1°C to 25.5°C
10
L2
L2
L2
E54
Fan 2 differential
0.1°C to 25.5°C
7
L2
L2
L2
E55
Fan control with ambient sensor - Min ambient -40°C to E56
0
L2
L2
L2
E56
Fan control with ambient sensor - Max
ambient
E55 to 110°C
20
L2
L2
L2
E57
Fan speed control with ambient sensor
0 to 100%
60
L2
L2
L2
E58
Condenser temperature/pressure threshold for
high alarm
-40°C to 110°C
-1.5 to 99.9 bar; -21 to 999 PSI
27.8
L2
L2
L2
E59
High condenser temperature alarm delay
0 to 255 min
0
L2
L2
L2
E60
High condenser temperature alarm with
compressor off
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2