C6.1.6/0117-1017/E
60
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
M17
Activation delay probe error
0 to 255 sec
1
L2
L2
L2
M18
% valve in case of probe error
0 to 100%
50
L2
L2
L2
M19
Time at initial steps at the start time
0 to 255 sec
30
L2
L2
L2
N01
Current minute
0 to 59
L1
L1
L1
N02
Current hour
0 to 23
L1
L1
L1
N03
Day of month
1 to 31
L1
L1
L1
N04
Month
1 to 12
L1
L1
L1
N05
Year
0 to 99
L1
L1
L1
P01
Compressor setpoint hysteresis in energy
saving mode
0.0 to 9.9 bar; 0. to 99.9 PSI;
0.0°C to 25.5°C
0
L2
L2
L2
P02
Condenser setpoint hysteresis in energy
saving mode
0.0°C to 25.5°C
0
L2
L2
L2
R01
Digital input 1 function
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
Not used
L2
L2
L2
R02
Digital input 1 polarity
oP (0) - CL (1)
CL
L2
L2
L2
R03
Activation delay for digital input 1
0 to 255 min
0
L2
L2
L2
R04
Digital input 2 function
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
High pressure input
N.V.
N.V.
N.V.
R05
Digital input 2 polarity
oP (0) - CL (1)
oP
N.V.
N.V.
N.V.
R06
Activation delay for digital input 2
0 to 255 min
0
N.V.
N.V.
N.V.