C6.1.6/0117-1017/E
70
Defrost with Real Time Clock
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
nu = Not used
EPt = Evaporator temperature
G12
Defrost probe selection
nu = Not used
EPt = Evaporator temperature
G23
Defrost interval mode
nu = Not used
rtC = Real time clock
S05
Relay output 2
nu = Not used
dEF = Defrost
G18
Interval between defrost cycles
4 min
Adjust to application requirements
G19
Maximum duration of defrost
20 min
Adjust to application requirements
G21
Defrost termination temperature
10
Adjust to application requirements
G26
Drip time
1 min
Adjust to application requirements
G28-41
See table 32 " Parameter list Level 1 & Level 2 (Pr1 & Pr2)"
[-] min
Adjust to application requirements
Defrost with evaporator fan
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
nu = Not used
EPt = Evaporator temperature
G12
Defrost probe selection
nu = Not used
EPt = Evaporator temperature
G23
Defrost interval mode
nu = Not used
In = By time (G18)
G42
Fans operating mode
Cn
Oy
S05
Relay output 2
nu = Not used
EPF = Evaporator fan
G18
Interval between defrost cycles
4 min
Adjust to application requirements
G19
Maximum duration of defrost
20 min
Adjust to application requirements
G21
Defrost termination temperature
10
Adjust to application requirements
G26
Drip time
1 min
Adjust to application requirements
G55
Fan delay after defrost
1 min
Adjust to application requirements
Unit On/Off
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
R07
Digital input 3 configuration
nu = Not used
OnF = On/Off
R08
Digital input 3 polarity
CL = Closed
Adjust to application requirements