Ident number 3012904 (052-2685-00) 

2/2

 

Quick Installation Guide 

 

How to pro

gram the parameters “Pr1” 

 

ACCESS 
to Pr1 

 

Press and hold for about 3 sec to have access to 
the first programming level (

Pr1

).  

Select 
item 

 or 

 

Select the parameter or submenu using the 
arrows. 

Show 
value 

 

Press 

SET 

button. 

Modify 

 or 

 

Use the arrows to modify the value. 

Confirm 
and store 

 

Press 

SET 

key: the value will blink for 3 sec, and 

then the display will show the next parameter. 

EXIT 

 

Instantaneous exit from the programming mode, 
otherwise wait for about an adjustable period of 
time (MTO) (without press any button). 

 
When entering first time the programming level the display shows label 

rtC

 (real time clock).  

 

By pushing 

 you have access to parameters N01/02/03/04/05 to adjust time & date. 

 

By pushing 

or 

 the label 

rtC 

will change to

 PAr, 

which is access to the programming level 1. Push 

 and the parameters of programming level 1 can be changed. 

 

The following parameters 

“Pr1” 

must be verified before commissioning 

 

 

Parameter 

Description 

Unit 

Factory 

Setting 

Comment 

C01 

Compressor cut in 
pressure set point 

[bar]* 

4.0 

Not used for Digital 
ZXDE 

C02 

Compressor cut out 
pressure set point 

[bar]* 

2.0 

Not used for Digital 
ZXDE 

C07 

refrigerant Selection for 
Regulation 

[-] 

R404A 

R22, R407A, R407F, 
R507, N40, DR33, 
R134a, R407C 

C16 

Digital compressor 
setpoint 

[bar]* 

3.3 

Not used for ZXM & ZXL 

C17 

Proportional band for 
compressor regulation 

[bar]* 

2.0 

Not used for ZXM & ZXL 

C21 

Cycle time for digital 
compressor 

[seconds] 

10 

Not used for ZXM & ZXL 

C24 

Minimum capacity for 
digital compressor 

[%] 

20 

Not used for ZXM & ZXL 

C25 

Maximum capacity for 
digital compressor 

[%] 

100 

Not used for ZXM & ZXL 

E39 

Condenser set point  

[°C] 

35.0 

 

E46 

regulation band of 
variable fan 

[°C] 

10.0 

 

N01 

Current Minute 

[-] 

[-] 

 

N02 

Current hour 

[-] 

[-] 

 

N03 

Day of Month 

[-] 

[-] 

 

N04 

Month 

[-] 

[-] 

 

N05 

Year 

[-] 

[-] 

 

T18 

Access to Pr2 level 

[-] 

[-] 

Password: 3 2 1 

o

 

*Pressures always considered as relative pressures 

 
 
NOTE

:  This document  is  for  quick  installation  purposes.  For  detailed  instructions, please  refer to  the 

Application Guidelines. 