C6.1.7/1110-0519/E
9
Parameter
EC2-552
F
Modulating parameters
Min
Max
Unit
Def
F2
Minimum output value
10
100
%
20
F3
Maximum output value
10
100
%
100
Table 5: Minimum and maximum output values
Minimum and maximum output values can be adjusted. In case of a single-compressor unit with a
Digital Scroll compressor; the maximum output could be set below 100% if the system requests
less than the maximum capacity. In that case
F3 > F2
.
NOTE: For further information, please refer to Application Guidelines C6.1.3 "
Condensing
Unit
Controller
for
Copeland
EazyCool
™
Outdoor
Condensing
Units"
available on