10
C6.1.7/1110-0519/E
3
Installation
WARNING
High pressure!
Injury to skin and eyes possible!
Be careful when opening
connections on a pressurized item.
HLR Digital Receiver units are delivered with a holding charge of neutral gas.
Since these units are used with remote condensers, they should be located in such a place to
prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins.
A clogged condenser will increase the condensing temperature, thus reducing the cooling capacity,
which could lead to a high-pressure switch tripping. Clean the condenser fins on a regular basis.
3.1 Receiver unit handling
3.1.1 Transport and storage
WARNING
Risk of collapse! Personal injuries!
Move units only with appropriate
mechanical or handling equipment according to weight. Keep in the upright
position. Respect stacking loads according to
Figure 4
. Do not stack
anything on top of the unit packaging. Keep the packaging dry at all times.
Respect the maximum number of identical packages which may be stacked on one
another, where "n" is the limiting number:
▪
Transport: n = 3
▪
Storage: n = 3
Figure 4: Maximum stacking loads for transport and storage
The unit without packaging must be handled by a forklift truck, while always taking into account the
centre of gravity of the unit.
3.1.2 Weights
Single-compressor unit
Tandem-compressor unit
Unit model
Weight [kg]
Unit model
Weight [kg]
Net*
Gross*
Net*
Gross*
HLR13-ZBD30KCE
68.3
88
HLR31-ZBDT60KCE
122.8
149
HLR13-ZBD45KCE
70.3
90
HLR31-ZBDT90KCE
125.8
152
HLR13-ZBD58KCE
95.3
115
HLR31-ZBDT116KCE
171.8
237
HLR13-ZBD76KCE
93.3
113
HLR31-ZBDT152KCE
180.3
315
Table 6: Weights