Status LED
Status LED Description
Status LED Troubleshooting Information
Yellow Alert LED
4 Flashes
Locked Rotor
Compressor is drawing current without
rotating or four consecutive compressor
trips after run time of 1-15 seconds
1. Low line voltage (contact utility if voltage at
disconnect is low)
2. Verify presence of all legs of power line
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
5. Verify operating current
Yellow Alert LED
6 Flashes
Missing Phase
Demand signal is present but current is
missing in one phase
1. Improper wiring. Correct order of phases in
wires
2. Failed contactor. Check contacts for pitting
3. Compressor current could be too low. Refer to
specifications.
4. Verify presence of all legs of power line
Yellow Alert LED
9 Flashes
Low Voltage Detected
Control voltage dips below 85V for
110V or 170V for 220V
1. Low line voltage (contact utility if voltage at
disconnect is low)
2. Check wiring connections
Red Alert LED
1 Flash
LOCKED OUT ON:
High Discharge Line Temperature Trip
See inside label to determine cut out
temp.
1. Possible loss of refrigerant charge
2. Blocked condenser
3. Verify that discharge valve is open
4. On low temperature scroll compressors check
liquid injection
Red Alert LED
4 Flashes
LOCKED OUT ON:
4 Consecutive Locked Rotors Detected
Compressor is drawing current without
rotating or four consecutive compressor
trips after run time of 1-15 seconds
1. Low line voltage (contact utility if voltage at
disconnect is low)
2. Verify presence of all legs of power line
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
5. Verify operating current
Red Alert LED
6 Flashes
LOCKED OUT ON:
10 Missing Phase Detections
Demand signal is present but current is
missing in one phase
1. Improper wiring. Correct order of phases in
wires.
2. Failed contactor. Check contacts for pitting.
3. Compressor current could be too low. Refer to
specifications.
4. Verify presence of all legs of power line
Red Alert LED
7 Flashes
LOCKED OUT ON:
1 Reverse Phase Detected
Demand signal is present but current is
not detected in the correct sequence
1. Improper wiring. Correct order of phases in
wires.
2. Compressor current could be too low. Refer to
specifications.
3. Verify presence of all legs of power line
CoreSense
™
Diagnostics Module Troubleshooting
(Continued)