of 9 VDC for checking – do not attempt to check 
continuity through the sensors with any other 
type of instrument. Any external voltage or 
current may cause damage requiring compressor 
replacement.

During normal operation, this resistance value 

a.

should read less than 4500 ohms ±20%.

If the M1-M2 contacts are open, the measured 

b.

S1-S2 value is above 2750 ohms ±20% and 
the compressor has been tripped less then 
30 minutes then the module is functioning 
properly.

If the S1-S2 wire leads read less than 2750 ohms 

±20% and the M1-M2 contacts are open, reset 
the module by removing the power to T1-T2 for a 
minimum of 5 seconds.

Replace all wire leads and use a voltmeter to verify 

the M1-M2 contacts are closed.

If the M1-M2 contacts remain open and S1-S2 are 

less than 2500 ohms, remove leads from the M1-
M2 contacts and jumper together; 

CAUTION: Compressor should start at this time. 
HOWEVER DO NOT LEAVE JUMPER IN PLACE FOR 
NORMAL SYSTEM OPERATIONS.  THE JUMPER IS 
USED FOR DIAGNOSTIC PURPOSES ONLY.

Go to Compressor Supply Voltage 

Troubleshooting.

Compressor Voltage Supply Troubleshooting

Remove phase sensing leads from the module 

from L1/L2/L3.

Use a voltmeter to measure the incoming 3 phase 

voltage on L1/L2/L3. WARNING:  L1/L2/L3 could 

be at a potential up to 600VAC.  

Ensure proper voltage on each phase.

Remove power to the module for a minimum of 5 

seconds to reset and replace all wire leads.  Re-
energize the module. If the M1-M2 contacts are 
open with proper voltage to T1-T2, L1/L2/L3 and 
proper resistance to S1-S2 then the module is 
faulty and should be replaced.

Oil Type

Polyol ester lubricant (POE) must be provided if the 
refrigeration scroll is used with HFC refrigerants.

Copeland Scroll refrigeration compressors intended 
for use with R22 are supplied with mineral oil.

Reference

Table 7 

for proper oil charge. See 

Form

93-11

 for a complete list of all Emerson approved 

lubricants.

Oil Management for Single Compressor 
Applications

If the oil level is above the sight glass, oil circulation 
rates greater than 1.5% may be experienced with 
the ZB50, ZB58, ZB66, ZB76, ZB88, ZB95 & ZB114 
compressors.  This is especially true in the larger 
compressors in 60 Hz applications.

Oil Management for Rack Applications

Copeland Scroll refrigeration compressors may be 
used on multiple compressor parallel rack applications. 
This requires the use of an oil management system to 
maintain proper oil level in each compressor crankcase. 
The sight glass connection supplied can accommodate 
the mounting of the oil control devices.

Unlike Semi-Hermetic compressors, the scrolls do 
not have an oil pump with accompanying oil pressure 
safety controls. Therefore, an external oil level control 
is required.

The OMB Oil Level Management Control combines the 
functions of level control and timed compressor shut-
off should the level not come back to normal within 
a set period of time. This device has been found to 
provide excellent performance in fi eld tests on Scroll 
compressors and is recommended for parallel system 
applications.

Note: Emerson Climate Technologies' Application 
Engineering Department should be contacted for 
approved oil management systems.

TABLE 7

COMPRESSOR OIL CHARGE

Model

Initial

Recharge

ZB50
ZB58
ZB66
ZB76
ZB88
ZB95
ZB114
ZB56
ZB68
ZB75
ZB92
ZB11M

85
85
110
110
110
110
110
140
140
140
140
140

81
81
106
106
106
106
106
137
137
137
137
137

Summary of Contents for Copeland Scroll ZB KC Series

Page 1: ...ion e g ZB92KC produces approximately 92 000 Btu H For actual compressor performance information please visit Emerson Climate Technologies Online Product Information at www emersonclimate com Operating Envelope The Copeland Scroll refrigeration models can be used with a variety of refrigerants Table 1 shows these selection options The operating envelopes are depicted in Figures 1A 1B 1C 1D 1E and ...

Page 2: ...ycle operation conditions accumulators may not be required An accumulator is required on single compressor systems when the charge limitations exceed those values listed in Table 2 On systems with defrost schemes or transient operations that allow prolonged uncontrolled liquid return to the compressor an accumulator is required unless a Figure 1D ZB KC excluding ZB95KC ZB114KC Application Envelope...

Page 3: ...r Crankcase heaters are required on systems when the system charge exceeds the recommended charge limit See Table 2 The listed crankcase heaters Table 3 are intended for use only when there is limited access The heaters are not equipped for use with electrical conduit Where applicable electric safety codes require heater lead protection a crankcase heater terminal box should be used Recommended cr...

Page 4: ...re Controls Both high and low pressure controls are required and the following are the minimum and maximum set points Refer to Table 4 for proper settings IPR Valve The 7 through 15 horsepower refrigeration scroll compressors DO NOT have an internal high pressure relief valve To provide safe operation a high pressure control set no higher than 445 psig must be used in all applications reference Ta...

Page 5: ...effect upon the long term contact resistance of the relay and may result in false compressor trips PLC operated control circuits may not always provide this minimum current In these cases modifications to the PLC control circuit are required Consult your application engineering department for details Phase Protection The INT69SCY module provides phase protection for the compressor The module sense...

Page 6: ...g leads CAUTION Use an Ohmmeter with a maximum TABLE 6 Emerson P N 071 0520 07 071 0520 05 071 0620 00 071 0641 00 Manufacturer P N T I 30AA201E Kriwan 69SC DV Kriwan 69SCY Kriwan 69SU T1 T2 Module Power Voltage Supply 120V 240V 120V 240V 120V 240V 120V 240V Frequency 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz M1 M2 Module Output Contacts Maximum Voltage N A 250VAC 250VAC 250VAC Maximum Current 5 Amp...

Page 7: ...n the module is faulty and should be replaced Oil Type Polyol ester lubricant POE must be provided if the refrigeration scroll is used with HFC refrigerants Copeland Scroll refrigeration compressors intended for use with R22 are supplied with mineral oil Reference Table 7 for proper oil charge See Form 93 11 for a complete list of all Emerson approved lubricants Oil Management for Single Compresso...

Page 8: ...tem Note The use of standard soft grommets is not recommended for our refrigeration scroll rack installations These softer mounts allow for excessivemovementthatwillresultintubebreakage unless the entire system is properly designed Connection Fittings There are various connection fittings available for Copeland Scroll refrigeration compressors The various options are shown in Table 8 Three Phase S...

Page 9: ... and oil mixture could ignite as it escapes and contacts the brazing flame It is important to check both the high and low sides with manifold gauges before unbrazing or in the case of assembly line repair remove refrigerant from both the high and low sides Instructions should be provided in appropriate product literature and assembly line repair areas Hi Pot Testing Copeland Scroll compressors are...

Page 10: ...icable reserve the right to modify the design or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser or end user CAUTION POE must be handled carefully and the proper protective equipment gl...

Reviews: