Figure 15: Example of ZF*K5E-TFD installation, liquid injection with DTC valve and discharge thermostat on the
discharge line
Assembly of the discharge line thermostat
For installation, please follow the recommendations below.
▪
Install the discharge line thermostat on the
discharge tube 120 mm from top cap.
▪
Snap the retainer clip over the tube and onto the
thermostat.
▪
The thermostat should be placed on the discharge
tube so that its body is in upward position on a
horizontal tube installation.
▪
Ensure that the thermostat is not tilted.
▪
The wire must not be in contact with the top cap of
the compressor or the discharge tube. Care should
be taken to route wires so that they do not come
into contact with sharp objects.
▪
To avoid any impact on tripping temperature by the
ambient, the discharge line thermostat must be
insulated.
▪
Wrap thermal insulation around the pipe left and
right of the thermostat and secure it with plastic
straps.
▪
Wrap a second layer of insulation around the first
one and around the thermostat and secure it with
plastic straps.
Discharge
thermostat
DTC valve cap
DTC valve