background image

 

20  Excessive Liquid Floodback 

The following tests are for those Air/Water system configurations and charge levels, which need special testing to 
verify exemption from the need of an accumulator. 
 

20.1 Continuous 

Floodback 

To test for excessive continuous liquid refrigerant floodback, it is necessary to operate the system in a test room at 
conditions where steady state floodback may occur (low ambient air/water heating). Thermocouples should be 
attached to the suction and discharge lines of the compressor (approximately 150 mm from the shell) and insulated. If 
the system is designed to be field charged it should be overcharged by 15 % in this test to simulate overcharging 
commonly found in field installations.  
The system should be operated at an indoor temperature of 20°C and outdoor temperature extremes (-18°C or lower) 
which produce floodback conditions. The compressor suction and discharge pressures and temperatures should be 
recorded. The system should be allowed to frost up for several hours (disabling the defrost control and spraying water 
on the outdoor coil may be necessary) to cause the saturated suction temperature to fall to -30°C or below. The 
compressor sump temperature must remain above the saturated suction temperature as determined from Figure 2 or 
design changes must be made to reduce the amount of floodback. If an accumulator is used an oil return orifice size 
of 1,4 mm is recommended.  
 

20.2  Repeated Floodback during Defrost 

For systems using hot gas bypass defrost, and having refrigerant charge levels above the limits given in Section 8 it 
may be necessary to fit an accumulator to trap a certain amount of the returning liquid. A good indication of liquid 
return can be low sump temperatures (Figure 2). Obtain a sample compressor with a side sight tube to measure liquid 
level in the compressor. Set the system up in a configuration with the indoor unit elevated approximately 1 m above 
the outdoor unit with approximately 7 m of connecting tubing with no traps between the indoor and outdoor units. If 
the system is designed to be field charged, the system should be overcharged by 15% in this test to simulate 
overcharging commonly found in field installations. Record the height of the liquid in the compressor during each 
cycle, any protector trips, or any compressor stalls during each test. Review all test results with Copeland Application 
Engineering to determine if an accumulator is required for the application. 
 

21 Installation 

Four vibration absorber grommets are supplied with each compressor (see Figure 10). They dampen the start-up 
surge of the compressor and prevent sounds and vibrations from being transmitted to the compressor base during 
operation to a large extent. The metal sleeve inside is intended as a guide to hold the grommet in place. It is not 
designed as a load-bearing member, and excessive torquing can crush the sleeve. Its inner diameter is approximately 
8.5 mm to fit e.g. an M8 screw. The mounting torque should be 13 ± 1 Nm. It is critically important that the grommet is 
not compressed. A clearance space of approximately 2-mm between the bottom of the washer and the top of the 
grommet spacer is recommended (see Figure 10). 
 

2mm

In Operation 

Figure 10: Mounting Parts 

 

C6.2.9/0203-1004/E 9 

Summary of Contents for Copeland Scroll ZH 15 K4E

Page 1: ...Scroll compressors for Dedicated Heat Pumps ZH15 K4E ZH45 K4E Application Guidelines ...

Page 2: ...perature Protection 5 10 Standard Motor Protection 6 11 Low Ambient Cut Out 6 12 Pressure Controls 6 13 Shut Off 6 14 Starting 6 15 Deep Vacuum Operation 6 16 Brief Power Interruptions 6 17 Electrical Installation 7 18 High Potential Testing 8 19 Compressor Functional Check 8 20 Excessive Liquid Floodback 9 20 1 Continuous Floodback 9 20 2 Repeated Floodback during Defrost 9 21 Installation 9 22 S...

Page 3: ...ting oils must be used Do not start the compressor until it is charged with refrigerant Correctly used the compressor and the pressure line piping may reach temperatures that may cause burning if touched Wear safety goggles when working on open systems If the refrigerant needs to be removed from the system do not disperse it in the environment use the correct equipment method of removal For storag...

Page 4: ...E Model Designation Z H 26 K 4 E TFD 524 1 2 3 4 5 6 7 8 1 Z Compressor family Z Scroll 2 H Dedicated heat pump compressor 3 Nominal heating capacity kW 50 Hz and 7 C evaporating 50 C condensing using multiplier 1 3 Ex 26K 8 6 kW 4 Nominal heating capacity multiplier K 1 M 10 5 Model variation 6 POE Oil 7 Motor version 8 Bill of Material 4 Application Envelope Tc C Te C R407C Mid point Figure 1 Ap...

Page 5: ...of the compressor Figure 2 Minimum bottom shell temperature tb One characteristic of POE is that it is far more hygroscopic than mineral oil Figure 3 Only brief exposure to ambient air is needed for POE to absorb sufficient moisture to make it unacceptable for use in a refrigeration system Since POE retains moisture chemically it is not possible to completely remove it through the use of vacuum Co...

Page 6: ...ot exceed the following values 3 6 kg for ZH 15 K4E ZH 26 K4E 4 5 kg for ZH 30 K4E ZH 45 K4E A CCH is to prevent refrigerant migrating into the shell during standstill periods It is recommended to fit a CCH if the compressor is located outside the building the system charge is above the limits shown and no accumulator is piped to provide free liquid drainage during the off cycle as shown For corre...

Page 7: ...startup low voltage starting characteristics are excellent for Copeland Scroll compressors 15 Deep Vacuum Operation The danger of pulling deep vacuums is avoided due to an internal low vacuum protection which prevents the scrolls pumping unloads when the pressure ratio exceeds approximately 20 1 In order to avoid nuisance trips it is recommended to set the low pressure control as described in Sect...

Page 8: ...n depending upon phasing of the power to L1 L2 and L3 Since there is a 50 50 chance of connecting power in such a way as to cause rotation in the reverse direction it is important to include notices and instructions in appropriate locations on the equipment to ensure proper rotation direction is achieved when the system is installed and operated Verification of proper rotation direction is made by...

Page 9: ...Compressor Functional Check It is not desirable to perform functional compressor tests where the compressor is turned on with the suction service valve closed to check how low the compressor will pull suction pressure Rather the following diagnostic procedure should be used to evaluate whether the Copeland Scroll compressor is functioning properly 1 Proper voltage to the unit should be verified 2 ...

Page 10: ...ge levels above the limits given in Section 8 it may be necessary to fit an accumulator to trap a certain amount of the returning liquid A good indication of liquid return can be low sump temperatures Figure 2 Obtain a sample compressor with a side sight tube to measure liquid level in the compressor Set the system up in a configuration with the indoor unit elevated approximately 1 m above the out...

Page 11: ...rch flame to area 2 Heat area 2 until braze temperature is attained moving the torch up and down and rotating around the tube as necessary to heat the tube evenly Add braze material to the joint while moving the torch around the joint to flow braze material around the circumference After the braze material flows around the joint move the torch to heat area 3 This will draw the braze material down ...

Page 12: ...and discharge line can briefly but repeatedly reach temperatures above 177 C as the compressor cycles on its internal protection devices Care must be taken to ensure that wiring or other materials which could be damaged by these temperatures do not come into contact with the shell 27 System Charging Procedure Rapid charging on only the suction side of a single phase Scroll equipped system or conde...

Page 13: ...ference is that the vibration characteristic of the Scroll compressor although low includes two very close frequencies one of which is normally isolated from the shell by the suspension of an internally suspended compressor These frequencies which are present in all compressors may result in a low level beat frequency that can be detected as noise coming along the suction line into a house under s...

Page 14: ...ska D 63477 Maintal P 02 673 Warszawa Tel 49 0 6109 6059 0 Tel 48 225 458 9205 Fax 49 0 6109 6059 40 Fax 48 225 458 9255 France Greece Maghreb Russia CIS 8 Allee Du Moulin Berger Malaya Trubetskaya 8 11th Floor F 69130 Ecully RUS 119881 Moscow Tel 33 0 4 78668570 Tel 7 095 232 94 72 Fax 33 0 4 78668571 Fax 7 095 232 03 56 Italia Middle East Africa Via Ramazzotti 26 PO Box 26382 R A 8 FD 2 I 21047 ...

Reviews: