Figure 11: Maximum thickness of cable shoe connectors
Cable glands have an influence on the protection class of the terminal box. It is strongly
recommended to use appropriate cable glands in order to reach the rated protection class.
Emerson Climate Technologies advises installers/service providers to pay attention to this
aspect every time they install or replace a Copeland Scroll compressor and to use cable glands
according to EN 50262 or any other relevant standard of application in their country/region.
Examples of correct electrical installations are shown in
Figures 12 & 13
below.
Figure 12: Correct electrical installation with cable glands for IP21 T-box, eg, model ZH04K1P
Figure 13: Correct electrical installation with cable glands for IP54 T-box (model ZHI46K1P)
4.2.3 Motor winding
The ZH Scroll compressors are offered with either a single-phase or a three-phase induction
motor, depending on the size. All three-phase motors are connected in star; single-phase motors
need a run capacitor.