C6.2.26/1013-1116/E
31
Condition
Cause
Corrective action
Low suction
pressure
System design
load too small
If the compressor is running in a tandem or in parallel,
modulate the running process.
Inadequate
refrigerant
going to the
evaporator
Lower normal discharge pressure values can lead to
insufficient refrigerant flow to the system.
This can also be verified by checking the evaporator
outlet superheat, if it is found unusually high. Check the
selection of the expansion valve (likely undersized).
Noise during shut-
off
Anti-reverse
device
This does not have any effect on the durability of the
compressor, no action is necessary.