background image

 

29 Shell 

Temperature 

Under rare circumstances caused by failure of system components such as the condenser or evaporator fan, or loss 
of charge, and depending on the type of expansion control, the top shell and discharge line can briefly but repeatedly 
reach temperatures above 177°C as the compressor cycles on its internal protection devices. Care must be taken to 
ensure that wiring or other materials, which could be damaged by these temperatures, do not come into contact with 
the shell. 
 

30  System Charging Procedure 

Rapid charging on only the suction side of a single-phase Scroll equipped system or condensing unit can occasionally 
result in a temporary no-start condition for the compressor. The reason for this is that if the flanks of the spirals 
happen to be in a sealed position, rapid pressurization of the low side without opposing high side pressure can cause 
the spirals to seal axially. As a result, until the pressures eventually equalize, the spirals can be held tightly together, 
preventing rotation. The best way to avoid this situation is to charge on both the high and the low side simultaneously 
at a rate which does not result in axial loading of the spirals. The maximum charging rate can be determined through 
simple tests. 
 

31  Unbrazing System Components 

Caution!

 Before opening a system, it is important to remove all refrigerants from both the high and low side. If the 

refrigerant charge is removed from a scroll-equipped unit by bleeding the high side only, it is possible for the scrolls to 
seal preventing pressure equalisation through the compressor. This may leave the low side shell and suction line 
tubing pressurised. If a brazing torch is then applied to the low side while the low side shell and suction line contains 
pressure, the pressurised refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame. To 
prevent this occurrence, it is important to check both the high and low side with manifold gauges before unbrazing. 
Instructions should be provided in appropriate product literature and assembly (line repair) areas. If compressor 
removal is required, the compressor should be cut out of system rather than unbrazed. 
 

32 Compressor 

Replacement 

In the case of a motor burn, the majority of contaminated oil will be removed with the compressor. The rest of the oil is 
cleaned through use of suction and liquid line filter dryers. A 100% activated alumina suction filter drier is 
recommended but must be removed after 72 hours. It is highly recommended that the suction accumulator be 
replaced if the system contains one. This is because the accumulator oil return orifice or screen may be plugged with 
debris or may become plugged shortly after a compressor failure. This will result in starvation of oil to the replacement 
compressor and a second failure. 
When a single compressor or tandem is exchanged in the field, a major portion of the oil may still be in the system. 
While this may not affect the reliability of the replacement compressor, the extra oil will add to rotor drag and increase 
power usage.  
See Section for Rotalock valve, flange fittings, sight glass, and mounting bolt torque’s values. 
 

33  Pressure Equipment Directive 

All Copeland Scroll compressors covered in this guideline conform to the European Pressure Equipment directive. 
The nameplate shows the PED marking CE 0062 with the refrigerant group and low side temperature. 

C6.2.16/1004/E 13 

Summary of Contents for Copeland Scroll ZH56 K4E ZH11 ME Series

Page 1: ...Scroll compressors for Dedicated Heat Pumps ZH56 K4E ZH11 ME Application Guidelines ...

Page 2: ...nt Cut Out 6 13 Pressure Controls 6 14 Shut off Sound 6 15 Starting 6 16 Deep Vacuum Operation 6 17 Electrical Installation 6 18 Electronic Motor Protection 7 19 Protector Functional Check and Failure Detection 8 20 High Potential Testing 9 21 Compressor Functional Check 9 22 Excessive Liquid Floodback 9 22 1 Continuous Floodback 9 22 2 Repeated Flood back during Defrost 10 23 Installation 10 24 S...

Page 3: ... start the compressor until it is charged with refrigerant Correctly used the compressor and the pressure line piping may reach temperatures that may cause burning if touched Wear safety goggles when working on open systems If the refrigerant needs to be removed from the system do not disperse it in the environment use the correct equipment method of removal For storage use original packaging and ...

Page 4: ... 524 1 2 3 4 5 6 7 8 1 Z Compressor family Z Scroll 2 H Dedicated heat pump compressor 3 Nominal heating capacity kW 50 Hz and 7 C evaporating 50 C condensing using multiplier 1 3rd 4 Nominal heating capacity multiplier K 1 M 10 5 Model variation 6 POE Oil 7 Motor version 8 Bill of Material 4 Qualified Refrigerant R407C has been qualified for the compressor models ZH56K4E ZH11ME 5 Application Enve...

Page 5: ...l temperature tb One characteristic of POE is that it is far more hygroscopic than mineral oil Figure 3 Only brief exposure to ambient air is needed for POE to absorb sufficient moisture to make it unacceptable for use in a refrigeration system Since POE retains moisture chemically it is not possible to completely remove it through the use of vacuum Compressors supplied by Copeland contain oil wit...

Page 6: ...grating into the shell during standstill periods It is recommended to fit a CCH if the compressor is located outside the building the system charge is above the limits shown For correct mounting location of a CCH please see Figure 5 Fig 5 Crankcase heater location 9 Screens The use of screens finer than 30 x 30 mesh 0 6 mm openings anywhere in the system is not recommended Field experience has sho...

Page 7: ...e tube of the compressor prevents high pressure gas entering the compressor after shut down Additionally there is a dynamic discharge valve mounted on the fixed Scroll which effectively eliminates reverse rotation 15 Starting During the very brief start up a short metallic sound is audible resulting from initial contacting of the spirals and is normal Due to the design of the Copeland Scroll the i...

Page 8: ...series is embedded in the motor windings so that the temperature of the thermistors can follow the winding temperature with little inertia An electronic module is required to process the resistance values and trip a control relay depending on the thermistor resistance The characteristic gradient of a thermistor resistance curve is shown in Figure 8 The resistance curve can be designed for differen...

Page 9: ...onnected and measured between the leads Resistance must be between 150 and 1250 ohms If the thermistor chain has a higher resistance 2750 Ohms or greater the motor temperature is still too high and it has to be allowed to cool If the resistor is 0 Ohms the compressor has to be exchanged due to shorted sensor circuit Ohms indicates an open sensor circuit and the compressor has to be replaced If no ...

Page 10: ... configuration and the system high potential tested again 21 Compressor Functional Check It is not desirable to perform functional compressor tests where the compressor is turned on with the suction service valve closed to check how low the compressor will pull suction pressure Rather the following diagnostic procedure should be used to evaluate whether the Copeland Scroll compressor is functionin...

Page 11: ...f the liquid in the compressor during each cycle any protector trips or any compressor stalls during each test Review all test results with Copeland Application Engineering to determine if an accumulator is required for the application 23 Installation Four vibration absorber grommets are supplied with each compressor see Figure 10 They dampen the start up surge of the compressor and prevent sounds...

Page 12: ... joint areas 2 and 3 slowly and uniformly until the braze material softens and the tube can be pulled out of the fitting To reconnect Recommended brazing materials Silfos with minimum 5 silver or silver braze used on other compressors Due to the different thermal properties of steel and copper brazing procedures may have to be changed from those commonly used For brazing of the tubes see Figure 11...

Page 13: ...ion line into a house under some conditions Elimination of the beat can be achieved by attenuating either of the contributing frequencies This is easily done by using one of the common combinations of design configuration described below A second difference of the Copeland Scroll compressor is that under some conditions the normal starting motion of the compressor can transmit an impact noise alon...

Page 14: ...hell and suction line tubing pressurised If a brazing torch is then applied to the low side while the low side shell and suction line contains pressure the pressurised refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is important to check both the high and low side with manifold gauges before unbrazing Instructions should be prov...

Page 15: ...Notes ...

Page 16: ...a D 63477 Maintal P 02 673 Warszawa Tel 49 0 6109 6059 0 Tel 48 225 458 9205 Fax 49 0 6109 6059 40 Fax 48 225 458 9255 France Greece Maghreb Russia CIS 8 Allee Du Moulin Berger Malaya Trubetskaya 8 11th Floor F 69130 Ecully RUS 119881 Moscow Tel 33 0 4 78668570 Tel 7 095 232 94 72 Fax 33 0 4 78668571 Fax 7 095 232 03 56 Italia Middle East Africa Via Ramazzotti 26 PO Box 26382 R A 8 FD 2 I 21047 Sa...

Reviews: