background image

16

© 2016 Emerson Climate Technologies, Inc.

AE4-1303 R15

Compressor Replacement after Motor Burn

In the case of a motor burn, the majority of 

contaminated oil will be removed with the compressor. 

The rest of the oil is cleaned through use of suction 

and liquid line filter dryers. A 100% activated alumina 

suction  filter  drier  is  recommended  but  must  be 

removed after 72 hours. See

 AE24-1105

 for clean up 

procedures and 

AE11-1297

 for liquid line filter-drier 

recommendations. 

NOTICE It is highly recommended that the suction 

accumulator be replaced if the system contains 

one.

 This is because the accumulator oil return orifice 

or screen may be plugged with debris or may become 

plugged shortly after a compressor failure. This will 

result in starvation of oil to the replacement compressor 

and a second failure. 

Manifolded Compressor Replacement

WARNING

When  lifing  manifolded  compressor  assemblies, 

all compressors must be lifted by their respective 

lifting rings. Use care and exercise extreme caution 

when lifting and moving compressors. Personal 

safety equipment must be used.

Should a compressor fail in a manifolded set, only the 

failed compressor should be replaced and not both 

compressors. The oil from the failed compressor will 

stay mostly in the failed compressor. Any contaminated 

oil that does enter the tandem circuit will be cleaned by 

the liquid line filter drier, and when used, the suction 

line filter drier.

The suction and discharge manifolds can be reused 

if the failed compressor is carefully removed and the 

manifolds are cut in such a way that a coupling and short 

piece of copper can reconnect the new compressor. A 

new oil equalization line can be field fabricated using 

3/8" (10mm) OD AC&R tubing, if one is needed. The 

replacement oil equalization line should be formed to 

exactly the same outline and dimensions as the line that 

is being replaced. To reconnect the oil equalization line 

to the compressor, the oil in one or both compressors 

will  have  to  be  lowered  below  the  oil  fitting  on  the 

compressor. To do this, oil should either be removed 

from the compressors or the compressors should be 

tilted back a minimum of 12 degrees from horizontal 

to move the oil away from the fitting (see 

Figure 10

).

Start-up of a New or Replacement Compressor

It is good service practice, when charging a system 

with a scroll compressor, to charge liquid refrigerant 

into the high side only. It is not good practice to dump 

liquid refrigerant from a refrigerant cylinder into the 

crankcase of a stationary compressor. If additional 

charge is required, charge liquid into the low side of 

the system with the compressor operating. 

WARNING! 

Do not start the compressor while the system is in 

a deep vacuum. 

Internal arcing may occur when any 

type of compressor is started in a vacuum. 

NOTICE

 

Do 

not operate the compressor without enough system 

charge to maintain at least 55 psig (3.8 bar) suction 

pressure for R-410A and 20 psig (1.4 bar) for R-22 

& R-407C. Do not operate with a restricted suction 

or liquid line. Do not operate with the low pressure 

cut-out disabled.

 Never install a system in the field and 

leave it unattended with no charge, a holding charge, or 

with the service valves closed without securely locking 

out the system. This will prevent unauthorized personnel 

from accidentally ruining the compressor by operating 

with no refrigerant flow.

As mentioned in the 

Manifolded Applications

 section, 

attention must be given to compressor oil levels 

when commissioning a new system and servicing an 

existing system. Oil levels should be checked with the 

compressor "off" and after the oil has had a chance 

to equalize between the compressors (for manifolded 

applications). If oil can't be seen in the sight-glass of the 

compressor, add oil until the sight-glass is approximately 

half full.

Field Trouble Shooting the Kriwan Module

Follow the steps listed below to trouble shoot the 

module in the field. See wiring diagram 

Figure 3

 or in 

terminal box cover.

1.  De-energize control circuit and module power. 

Remove the control circuit wires from the module 

(Terminals M1 & M2). Connect a jumper across 

these “control circuit” wires. This will bypass the 

“control contact” of the module. 

CAUTION ! The motor protection system within 

the compressor is now bypassed. Use this 

configuration to temporarily test module only.

Re-energize the control circuit and module power.
If the compressor will not operate with the jumper 

installed, then the problem is external to the solid 

state protection system. 

Summary of Contents for Copeland Scroll ZP KC Series

Page 1: ...tion Test Summary 11 Continuous Floodback Test 12 Field Application Test 12 Assembly Line Procedures Compressor Handling 12 Mounting 13 Suction Discharge Fittings 13 Assembly Line Brazing Procedure 13 Unbrazing System Components 13 Pressure Testing 13 Assembly Line System Charging Procedures 14 Electrical Connections 14 Hipot Testing 14 Tandem Assembly 14 Service Procedures Field Replacement 15 Mo...

Page 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Page 3: ...ety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system commponents Personal safety equipment must be used Failure to follow these warnings could result in serious personal...

Page 4: ... compressors Some of this information is recommended whereas other guidelines must be followed The Application Engineering department will always welcome suggestions that will help improve these types of documents Operating Envelope NOTICE It is essential that the glide of R 407C is carefully considered when adjusting pressure and superheat controls Figure 2 illustrates the operating envelopes for...

Page 5: ...nded for loss of charge protection and other system fault conditions that may result in very low evaporating temperatures Even though these compressors have internal discharge temperature protection loss of system charge will result in overheating and recycling of the motor overload protector Prolonged operation in this manner could result in oil pump out and eventual bearing failure The low press...

Page 6: ...refrigerant over initial 20 pounds Other system components such as shell and tube evaporators can trap significant quantities of oil and should be considered in overall oil requirements Reheat coils and circuits that are inactive during part of the normal cycle can trap significant quantities of oil if system piping allows the oil to fall out of the refrigerant flow into the inactive circuit The o...

Page 7: ...o control refrigerant during heating may not require an accumulator if testing assures the system designer that there will be no flood back throughout the operating range To test for flood back conditions and to determine if the accumulator or TXV design is adequate please see the section entitled Application Tests A large area protective screen no finer than 30x30 mesh 0 6mm openings is required ...

Page 8: ...charge pressures will go outside of the normal operating envelope The sound that the compressor makes during this transition period is normal and the duration of the sound will depend on the coil volume outdoor ambient and system charge level The preferred method of mitigating defrost sound is to shut down the compressor for 20 to 30 seconds when the reversing valve changes position going into and...

Page 9: ...s been achieved CAUTION POE must be handled carefully and the proper protective equipment gloves eye protection etc must be used when handling POE lubricant POE must not come into contact with any surface or material that might be harmed by POE including without limitation certain polymers e g PVC CPVC and polycarbonate Three Phase Scroll Compressor Electrical Phasing NOTICE Compressors that emplo...

Page 10: ...and reliability are its critical design characteristics Two different oil balancing techniques are used with tandems in this family of compressors two phase tandem line TPTL and oil equalization line OEL For trio assemblies only the TPTL design has been qualified The TPTL design is a larger diameter pipe connecting the oil sumps of the individual compressors allowing both gas and oil to flow betwe...

Page 11: ...l compressors that have TW electrical codes and TE electrical codes respectively Models with a W or E in the electrical code i e ZP182KCE TWD have a motor overload system that consists of an external electronic control module connected to a chain of four thermistors embedded in the motor windings The module will trip and remain off for a minimum of 30 minutes if the motor temperature exceeds a pre...

Page 12: ...ack Field Application Test To test for repeated excessive liquid flood back during normal system off cycles perform the Field Application Test that is outlined in Table 2 Obtain a sample compressor with a sight tube to measure the liquid level in the compressor when it is off Note The sight tube is not a good liquid level indicator when the compressor is running because the top of the sight tube i...

Page 13: ...nearby temperature sensitive parts Fire extinguishing equipment should be accessible in the event of a fire Figure 6 discusses the proper procedures for brazing the suction and discharge lines to a scroll compressor NOTICE It is important to flow nitrogen through the system while brazing all joints during the system assembly process Nitrogen displaces the air and prevents the formation of copper o...

Page 14: ... to keep the terminal box completely sealed Oversized conduits poor conduit connections to the terminal box an incorrectly installed terminal box cover or a missing terminal box cover gasket are a few possible air leakage paths CAUTION Moisture from warm moist air that is permitted to freely enter the terminal box can condense into droplets of water inside the cooler terminal box of the compressor...

Page 15: ...compressor family BR that can be replaced by this scroll compressor family The mounting dimensions of the older scroll and the reciprocating compressor are 8 65 X 8 65 220mm X 220mm to the center of the mounting holes The newer scroll has a mounting dimension of 7 5 X 7 5 190mm X 190mm To help adapt to this new dimension use mounting kit 922 0001 00 that contains an adaptor plate and mounting bolt...

Page 16: ...of 12 degrees from horizontal to move the oil away from the fitting see Figure 10 Start up of a New or Replacement Compressor It is good service practice when charging a system with a scroll compressor to charge liquid refrigerant into the high side only It is not good practice to dump liquid refrigerant from a refrigerant cylinder into the crankcase of a stationary compressor If additional charge...

Page 17: ...cement module must have the same supply voltage rating as the original module NOTE The Kriwan INT69 SU2 has been phased out of production by Kriwan Kriwan modules that require replacement in the field should be replaced with the CoreSense Communications module listed in Table 4 Kriwan to CoreSense retrofit instructions are listed at the end of this bulletin Field Troubleshooting CoreSense Communic...

Page 18: ...ne third of compressors returned to Emerson Climate Technologies Inc for warranty analysis are determined to have nothing found wrong They were misdiagnosed in the field as being inoperable Replacing working compressors unnecessarily costs everyone Refrigerant Retrofits NOTICE ZR compressors are UL recognized for use with R 22 R 407C or R 134a only Use of any other refrigerants will void the compr...

Page 19: ...19 2016 Emerson Climate Technologies Inc AE4 1303 R15 Figure 1 ...

Page 20: ... 60 70 80 Evapora ng Temperature C Condensing Temperature C Condensing Temperature F Evapora ng Temperature F R 407C R 22 R 134a 50 60 Hertz Operation 34 24 14 4 6 16 26 4 14 24 34 44 54 64 40 50 60 70 80 90 100 110 120 130 140 150 160 30 20 10 0 10 20 30 40 50 60 70 80 90 Evapora ng Temperature C Condensing Temperature C Condensing Temperature F Evapora ng Temperature F R 410A 50 60 Hertz Operati...

Page 21: ...RA CICLADO FRECUENTE 1 1 0 9 600 19 200 EVEN PAR STANDALONE DESCONECTADODELARED ENABLE ACTIVADO DISABLE DESACTIVADO 0 NONE NINGUNA LOCKOUT PERDIDA DE FUNCION WARNING PRECAUCION WARNING PRECAUCION NETWORK CONECTADOALARED LOCKOUT TRIP PERDIDA DE FUNCION INTERRUPCION DE FUNCION 4 N A N A 5 WARNING PRECAUCION FUTURE USE USO FUTURO SHORT CYCLING CICLO FRECUENTE 8 N A FUTURE USE USO FUTURO SYMBOLS SIMBO...

Page 22: ...22 2016 Emerson Climate Technologies Inc AE4 1303 R15 Figure 4 ASTP Label ...

Page 23: ...23 2016 Emerson Climate Technologies Inc AE4 1303 R15 ZR84 144KC ZP90 137KC ZR160 190KC ZP154 182KC Figure 5 Crankcase Heater Location ...

Page 24: ...be Recommended brazing materials Any silfos material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure suction tube fitting I D and suction tube O D are clean prior to assembly If oil film is present wipe with denatured alcohol Dichloro Trifluoroethane or other suitable solvent Using a double tipped torch apply heat inArea 1 As tube approaches brazing temp...

Page 25: ...quired Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required acts as dampening mass Table 3 Design Configurations Outdoor Ambient 85 F 29 C 95 F 35 C 105 F 40 C System On Time Minutes 7 14 54 System Off Time Minutes 13 8 6 Number of On Off Cycles 5 5 4 Table 2 Field Application Te...

Page 26: ...1 100 0550 01 100 0550 01 Molded Plug TF Electricals Only 529 0099 00 529 0099 00 Protection Kriwan Module 120 240V not required replace with CoreSense not required replace with CoreSense Kriwan Module 24 V not required not required Kriwan Diagnose Module 120 240V not required 971 0641 00 not required 971 0641 00 Kriwan Diagnose Module 24 V not required 971 0641 01 not required 971 0641 01 CoreSen...

Page 27: ...93 257KC 24 10 9 ZPT308 364KC 27 12 2 ZPU274 336KC 27 12 2 Even Tandem Assembly Uneven Tandem Assembly Note Refer to AE4 1365 for ZP104 and ZP122 Table 6 Torque Values Part Torque ft lb in lb N m Sight Glass TPTL Rotalock Fitting 74 81 885 975 100 110 Discharge Rotalock Valve 95 103 1150 1240 130 140 Suction Rotalock Valve 125 132 1505 1593 170 180 Schrader Valve 3 3 5 0 40 60 4 5 6 8 Terminal Blo...

Page 28: ...de 3 Short Cycling Run time of less than 1 minute number of short cycles exceeds 48 in 24 hours 48 short cycles in 24 hours 1 Check system charge and pressure control setting 2 Adjust set point of temperature controller 3 Install anti short cycling control Green Flash Code 4 Not used with this compressor family N A N A N A Green Flash Code 5 Future Use N A N A N A Table 7 Protector Specifications ...

Page 29: ...mand 1 Check system charge and pressure control setting 2 Adjust set point of temperature controller 3 Install anti short cycling control Red Flash Code 4 Not used with this family of compressors N A N A N A Red Flash Code 5 Future Use N A N A N A Red Flash Code 6 Missing Phase Missing phase Lockout after 10 consecutive Alerts After 5 minutes and missing phase condition is not present 1 Check inco...

Page 30: ...gies Inc AE4 1303 R15 Figure 10 Tilted Tandem 12 Tilting the Compressor For Installation of the Oil Equalization Line Oil Equalization Line Oil Equalization Line Two Phase Tube Line Figure 9 Tandem Oil Balancing Two Phase Tandem Line ...

Page 31: ...ommunications 1 Disconnect and lock out the power to the unit 2 Using a straight blade screwdriver carefully depress the tabs holding the terminal cover to the terminal box to remove the terminal cover Before proceeding use a volt meter to verify that the power has been disconnected from the unit 3 Verify the Kriwan module part number matches one of those shown in the table below APPENDIX 1 Kriwan...

Page 32: ...12 Connect the L1 L2 and L3 phase sensing wires to the L1 L2 and L3 compressor terminal block connections See the compressor terminal cover wiring diagram for identification of the L1 L2 and L3 connections on the compressor terminal block 13 Double check the installation and make sure all connections are secure Install the compressor terminal cover 14 The module change is complete and the system c...

Reviews: