background image

7

© 2016 Emerson Climate Technologies, Inc.

AE4-1402 R4

lead to compressor overheating. A low pressure cut-out 

switch located in the suction line with a cut-out setting 

no lower than 20 psig (1.4 bar) is required in all heat 

pump applications. For air conditioning units, a cut-out 

setting no lower than 55 psig (3.8 bar) will adequately 

protect against most low pressure faults. A higher level 

of protection for air conditioning units can be realized 

if the cut-out setting is increased to 95 psig (6.6 bar) to 

prevent evaporator coil icing.

Discharge Temperature Protection

CAUTION

Compressor top cap temperatures can be very 

hot. Care must be taken to ensure that wiring or 

other materials which could be damaged by these 

temperatures do not come into contact with these 

potentially hot areas.

The ZPV063 compressors do not have an internal 

discharge gas temperature protection. In order for the 

variable speed drive to operate properly a thermistor 

should be attached to the compressor discharge line 

as close as possible and less than 6'' (15cm) from the 

compressor discharge fitting. The thermistor is designed 

for a 7/8" (22 mm) line and should be properly insulated. 

See 

Table 6

 of 

AE-1328

 for thermistor temperature vs 

resistance values. Refer to 

Table 1

 for part numbers 

of discharge line thermistors. 

Figure 7

 illustrates the 

discharge thermistor.

Motor Overload Protection

The drive will provide motor over current protection in 

the event the compressor becomes mechanically locked 

or if the load on the compressor motor is abnormally 

high. The input power supply to the drive must be 

properly fused. 

Oil Type

The variable speed scrolls are charged with polyolester 

(POE) oil. See the compressor nameplate for the 

original oil charge. A complete recharge should be 

approximately four fluid ounces (118cc) less than the 

nameplate value. Copeland

 Ultra 32-3MAF, available 

from Emerson Wholesalers, should be used if additional 

oil  is  needed  in  the  field.  Mobil  Arctic  EAL22CC, 

Emkarate RL22, Emkarate 32CF and Emkarate 3MAF 

are acceptable alternatives.

CAUTION! POE oil must be handled carefully and 

the proper protective equipment (gloves, eye 

protection, etc.) must be used when handling POE 

lubricant. POE must not come into contact with any 

surface or material that might be harmed by POE, 

and spills should be cleaned up quickly with paper 

towels, soap and water.

Maximum Tilt Angle

Applications, such as transportation air conditioning or 

mobile radar applications, may require the compressor 

to operate at some angle from vertical. Service 

personnel may be required to maneuver a unit through 

a stairwell or other cramped area that might require 

tilting the unit. The maximum allowable tilt angles from 

horizontal for individual compressors (not tandem or trio 

applications) are summarized below:

Max. tilt angle with compressor running = 15° 
Max. tilt angle with compressor not running = 60°

Contaminant Control

Copeland Scroll

 compressors leave the factory with 

a miniscule amount of contaminants. Manufacturing 

processes have been designed to minimize the 

introduction of solid or liquid contaminants. Dehydration 

and purge processes ensure minimal moisture levels 

in the compressor and continuous auditing of lubricant 

moisture levels assure that moisture isn’t inadvertently 

introduced into the compressor.

Moisture levels should be maintained below 50 ppm 

for optimal performance. 

A  filter-drier  is  required 

on all R-410A and POE lubricant systems to 

prevent solid particulate contamination, oil 

dielectric strength degradation, ice formation, oil 

hydrolysis, and metal corrosion.

 It is the system 

designer’s responsibility to make sure the filter-drier is 

adequately sized to accommodate the contaminants 

from system manufacturing processes that leave 

solid or liquid contaminants in the evaporator coil, 

condenser coil, and interconnecting tubing plus any 

contaminants  introduced  during  the  field  installation 

process. Molecular sieve and activated alumina are 

two filter-drier materials designed to remove moisture 

and mitigate acid formation. A 100% molecular sieve 

filter  can  be  used  for  maximum  moisture  capacity. A 

more conservative mix, such as 75% molecular sieve 

and 25% activated alumina, should be used for service 

applications.

Refrigerant Piping

Particular attention must be given to the system 

refrigerant pipe size with the variable speed scrolls. 

ASHRAE guidelines for pipe sizing should be followed 

Summary of Contents for Copeland Scroll ZPV063

Page 1: ...or Overload Protection 7 Oil Type 7 Maximum Tilt Angle 7 Contaminant Control 7 Refrigerant Piping 8 Discharge Check Valve 8 Suction and Discharge Tube Design 8 Compressor Mounting 9 Discharge Mufflers 9 Airborne Sound Control 9 Expansion Devices 9 Reversing Valves 9 Accumulators 10 Off Cycle Migration Control 10 Manifolded Compressors 10 Manifolded Applications 10 Application Tests General Applica...

Page 2: ...e compessor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could re...

Page 3: ...ectrically locking out the system Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Perso...

Page 4: ...ying conductors RLA MCC 1 4 Max Operating Current The maximum input current to the drive at nominal voltage when the compressor is running inside any one of the operating envelopes at the speed range designated for that envelope Please refer to Table 1 for more technical data for the compressor Power Supply The compressor and drive are an integral and optimized combination The drive will convert t...

Page 5: ...1 drive includes an oil boost cycle when the compressor operates between 1000 and 1800 RPM The oil boost cycle starts once the compressor operates for two hours between 1000 and 1800 RPM During the oil boost cycle the drive forces the compressor to run for five minutes at 3600 RPM After operating for five minutes at 3600 RPM the drive allows the compressor to operate between 1000 and 1800 RPM Figu...

Page 6: ...t in oil pump out if the system has long interconnecting piping Customers that choose to operate in these higher evaporating temperature areas should use a compressor sample with a sight tube during system development testing to ensure that an adequate level of oil is maintained in the compressor sump Sight tubed compressors for monitoring the oil level are available by contacting Application Engi...

Page 7: ...r protective equipment gloves eye protection etc must be used when handling POE lubricant POE must not come into contact with any surface or material that might be harmed by POE and spills should be cleaned up quickly with paper towels soap and water Maximum Tilt Angle Applications such as transportation air conditioning or mobile radar applications may require the compressor to operate at some an...

Page 8: ...of the sight glass The compressor oil level should be checked with the compressor off to avoid the sump turbulence when the compressor is running These compressors are available to the OEM with a production sight glass that can be used to determine the oil level in the compressor in the end use application These compressors are also available to the OEM with an oil Schrader fitting on the side of ...

Page 9: ... not have the ability to control the refrigerant flow across a wide range of operating pressures and flow rates required by the variable capacity system To better control superheat an electronic expansion valve EXV is recommended Electronic expansion valves have the ability to more precisely control superheat at lower settings over a wider operating range than a TXV They also have the capability t...

Page 10: ...d to at least 100 Watts when the compressor is off To use fewer than 100 Watts or to comply with future DOE requirements for off cycle power consumption off cycle migration testing must be performed A 70 watt crankcase heater may be used instead of the motor windings to provide heat to the base CAUTION Stator heat for off cycle migration must not be energized when the system is in a vacuum or if t...

Page 11: ...w system designs should be evaluated throughout the entire expected operating range of the unit to ensure the system will perform reliably throughout the life of the product Test data taken throughout the operating range of the unit should be closely scrutinized to help identify gross errors in system design that may produce conditions that could lead to compressor failure General Application Test...

Page 12: ...rmally low suction pressures during charging NOTICE Do not operate the compressor without enough system charge to maintain at least 55 psig 3 8 bar suction pressure Do not operate the compressor with the low pressure cut out disabled Do no operate with a restricted suction or liquid line Depending on the discharge pressure allowing pressure to drop below 55 psig 3 8 bar for more than a few seconds...

Page 13: ...damage to the drive Measuring the current in the three individual wires feeding the compressor will provide no useful information to the service technician other than to show that each winding of the compressor is drawing current The more appropriate measurement is the current input to the drive Current input to the drive can be compared to the published values of MCC and RLA Compressor Replacemen...

Page 14: ...ndem Cubic Centimeters Per Revolution 3 numeric characters Optional E POE Oil P POE R410A 1st Generation VS Only K1 Nominal Capacity Capacity at Rating Condition Multiplier 2 3 numeric characters K 1 000 M 10 000 C SCFM VARIABLE SPEED COMPRESSOR NOMENCLATURE Application Range Code Application Refgn Substance Compressed P AC HP R 410A B H Heat Pump Optimized R410A Figure 1 Compressor Nomenclature E...

Page 15: ...75 80 85 90 Tcond F Tevap F ZPV063 Operating Envelope 20 F 11 C SH 15 F 8 C SC 95 F 35 C Ambient Solid Line Boundaries OEM tes ng is required to monitor the DLT in the dashed line boundaries 2600 6000 RPM 2200 6000 RPM 1800 7200 RPM Tcond C Tevap C DLT 275 F 1000 7200 RPM An Oil Boost Cycle Is Required For Speeds 1000RPM 1800RPM Cycle Parameters 1000RPM 1800RPM For 2 Hours Ramp To 3600RPM For 5 Mi...

Page 16: ...ise superheat A cold sump may result in high refrigerant migration after shut down Figure 4 Oil Dilution Chart 30 25 20 15 10 5 0 5 10 24 14 4 6 16 26 36 10 0 10 20 30 40 50 60 70 80 90 100 110 20 10 0 10 20 30 40 50 Evaporating Temperature C Compressor Sump Temperature C Compressor Sump Temperature F Evaporating Temperature F 200 F 93 3 C Max Oil Temp Acceptable Unacceptable Too Much Refrigerant ...

Page 17: ... Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Field Service WARNING Remove refrigerant charge...

Page 18: ...18 2016 Emerson Climate Technologies Inc AE4 1402 R4 Figure 6 ...

Page 19: ...arge Thermistors Fluid Brake Sight Glass Floating Seal 7 8 22 3mm Discharge Fitting 1 1 8 28 7mm Fixed Scroll BPM Motor Orbiting Scroll Counterweight Cup for Oil Circulation Positive Displacement Oil Pump Suction Fitting Management Figure 8 ZPV063 Cross Sectional View ...

Page 20: ...E 1 E 9 X X X First Character Second Character Third Character Follows VS Motor Type VS Fixed Tandem Follows Fixed Electrical Code E E E E F Z E W Y X E B X F C X W G Examples 2E9 TFD 2ZD 3X9 TF7 3C7 4E9 TE5 4E5 5X9 TEE 5BE Figure 9 Electrical Nomenclature For Multiples ...

Page 21: ...scharge Line Thermistor 085 0261 00 ZPV063 Fits 7 8 Tube Discharge Line Thermistor Molex Connector 085 0211 00 ZPV063 Fits 7 8 Tube Thermistor Clip 032 0688 04 ZPV063 7 8 Clip Suction Discharge Discharge Rotalock O Ring Seal 020 0028 02 ZPV063 Suction Rotalock O Ring Seal 020 0028 03 Discharge Rotalock Service Valve 7 8 998 0510 90 Suction Rotalock Service Valve 1 1 8 998 0510 99 Discharge Rotaloc...

Page 22: ... 1 Motor Poles 6 Motor Input Frequency Hertz 50 360 Recommended Switching Frequency Hertz 6 000 Table 2 Compressor Motor Specifications Drive Model EVC1150B K1 114 EVC1150B L1 114 EVC1150B J1 114 Compressor Model ZPV0631E 4E9 ZPV0631E 4E9 ZPV0631E 5E9 Drive Voltage Input 380 480 500 575 200 240 Drive Nominal Power 15 KW 15 KW 15 KW Drive Max Continuous Output Current 31 Amps 27 Amps 58 Amps NOTE C...

Page 23: ...s kg ZPV063 15 7 18 8 18 8 Charge allowance for system Speed Range RPM Default RPM Acceleration RPM Sec Deceleration RPM Sec Notes Range Default Range Default Start 3600 7200 3600 400 1000 1 0 NA NA 1 Run 1000 7200 200 RPM S Stop 1000 7200 3600 or Envelope Minimum NA NA 50 500 2 0 2 3 4 Notes 1 Once the compressor reaches 3600 RPM hold for two minutes prior to accelerating or decelerating 2 If env...

Reviews: