AGL_AC_ST_YRH_EN_Rev01
15
Three-phase compressors (TF*):
Power circuit
Control circuit
Motor terminal connections
Three-phase compressors are connected to the
T1, T2 and T3 connections
Legend
B1 ............... System controller
K1, K2 ..... Contactors
B3 ............... Discharge gas thermostat
Q1 ........... Main switch
F1, F6, F8 ... Fuses
R2 ........... Crankcase heater
F3 ............... HP limiter
S1 ........... Auxiliary switch
F4 ............... LP limiter
RCD ........ Residual current device
Figure 14: Wiring diagrams for three-phase compressors with internal motor protection
4.3 Terminal box
– IP56
WARNING
Ignition source in a potentially flammable atmosphere! Fire hazard!
Particular attention must be paid in flammable refrigerant systems as any work
on the energized terminals in the compressor terminal box could create an
ignition. Do not touch the energized terminals with a tool or cable when the
compressor is energized.
Compressors operating with flammable refrigerants shall use only the qualified
terminal box supplied with the compressor.
CAUTION
Mechanical stress or shock! Overheating! Terminal Fusite damage and
leakage!
Mechanical stress and shocks to the Fusite must be avoided as they
could damage the glass and/or ceramic. This might result in hermetic failure
or loss of terminal performance. Precautions are required to prevent striking
or bending of pins. Bent or damaged pins may result in loss of hermeticity
and/or terminal performance.
Ensure correct connection of cables to the compressor terminal Fusite to avoid
local overheating of Fusite pins which might lead to refrigerant leaks.
All YRH(V)*KTE/KTG horizontal scroll compressors are equipped with a metal terminal box with an
IP56 protection class.