background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

1/4"  push-on  flag  type  terminals,  nor  the  terminal  block 
that requires ring terminals. 

Deep Vacuum Operation 

Copeland  Scroll  compressors  incorporate  internal  low  
vacuum  protection  and  will  stop  pumping  (unload)  when  
the  pressure  ratio  exceeds  approximately  10:1.  There  
is  an  audible  increase  in  sound  when  the  scrolls  start  
unloading. 

CAUTION!  Copeland  Scroll  compressors  (as  with  
any  refrigerant  compressor)  should  never  be  used  
to    evacuate    a    refrigeration    or    air    conditioning  
system.  The  scroll  compressor  can  be  used  to  pump  
down  refrigerant  in  a  unit  as  long  as  the  pressures  
remain  within  the  operating  envelope  shown  in  Figure  7.  
Prolonged  operation  at  low  suction  pressures  will  result  
in  overheating  of  the  scrolls  and  permanent  damage  to  
the  scroll  tips,  drive  bearing  and  internal  seal.  See  AE  
24-1105 for proper system evacuation procedures. 

Shell Temperature 

CAUTION 

Compressor  top  cap  temperatures  can  be  very  
hot. Care must be taken to ensure that wiring or 
other  materials  which  could  be  damaged  by  these 
temperatures  do  not  come  into  contact  with  these 
potentially hot areas. 

Certain  types  of  system  failures,  such  as  condenser  
or  evaporator  fan  blockage  or  loss  of  charge,  may  
cause  the  top  shell  and  discharge  line  to  briefly  or  
repeatedly  reach  temperatures  above  350°F  (177°C)  
as  the  compressor  cycles  on  its  internal  overload  
protection  device.  Care  must  be  taken  to  ensure  that  
wiring  or  other  materials  which  could  be  damaged  by  
these  temperatures  do  not  come  into  contact  with  these  
potentially hot areas. 

Suction and Discharge Fittings 

Copeland  Scroll  compressors  have  copper  plated  steel  
suction  and  discharge  fittings.  These  fittings  are  far  
more rugged and less prone to leaks than copper fittings  
used  on  other  compressors.  Due  to  the  different  thermal  
properties  of  steel  and  copper,  brazing  procedures  
may  have  to  be  changed  from  those  commonly  used.  
See  Figure  8  for  assembly  line  and  field  brazing  
recommendations. 

System Tubing Stress 

System  tubing  should  be  designed  to  keep  tubing 
stresses  below  9.5  ksi  (62  MPa),  the  endurance  limit 
of  copper  tubing.  Start,  stop  and  running  (resonance) 
cases should be evaluated. 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

Three Phase Scroll Compressor Electrical Phasing 

Copeland  Scroll  compressors,  like  several  other  types  
of  compressors,  will  only  compress  in  one  rotational  
direction.  Direction  of  rotation  is  not  an  issue  with  
single  phase  compressors  since  they  will  always  start  
and  run  in  the  proper  direction  (except  as  described  in  
the  section 

“Brief  Power  Interruptions”).  Three  phase  

compressors  will  rotate  in  either  direction  depending  
upon phasing of the power. Since there is a 50% chance  
of connecting power in such a way as to cause rotation  
in  the  reverse  direction,  it  is  important  to  include  
notices  and  instructions  in  appropriate  locations  
on  the  equipment  to  ensure  that  proper  rotation  
direction  is  achieved  when  the  system  is  installed  
and  operated.  Verification  of  proper  rotation  direction  
is  made  by  observing  that  suction  pressure  drops  and  
discharge  pressure  rises  when  the  compressor  is  
energized.  Reverse  rotation  will  result  in  no  pressure  
differential as compared to normal values. A compressor  
running  in  reverse  will  sometimes  make  an  abnormal  
sound. 

There  is  no  negative  impact  on  durability  caused  by  
operating  three  phase  Copeland  Scroll  compressors  in  
the  reversed  direction for  a  short  period  of  time (under  
one  hour).  After  several  minutes  of  reverse  operation,  
the  compressor

’s  internal  overload  protector  will  trip  

shutting  off  the  compressor.  If  allowed  to  repeatedly  
restart and run  in reverse  without correcting the situation,  
the  compressor  bearings  will  be  permanently  damaged  
because of oil loss to the system. All three-phase scroll  
compressors  are  wired  identically  internally.  As  a  result,  
once  the  correct  phasing  is  determined  for  a  specific  
system  or  installation,  connecting  properly  phased  
power  leads  to  the  identified  compressor  electrical  
(Fusite

™)  terminals  will  maintain  the  proper  rotational  

direction  (see  Figure  4).  It  should  be  noted  that  all  
three  phase scrolls  will continue to run  in reverse  until  
the  internal  overload  protector  opens  or  the  phasing  is  
corrected. 

Brief Power Interruptions 

Brief  power  interruptions  (less  than  ½  second)  may  
result  in  powered  reverse  rotation  of  single-phase  
Copeland  Scroll  compressors.  This  occurs  because  
high-pressure   discharge   gas   expands   backward  
through  the  scrolls  during  interruption,  causing  the  scroll  
to orbit in the reverse direction. When power is reapplied  
while  reverse  rotation  is  occurring,  the  compressor  may  
continue  to run  in  the  reverse  direction  for  some  time  
before  the  compressor

’s internal overload trips. This will  

not  cause  any  damage  to the  compressor,  and  when  
the  internal  overload  resets,  the  compressor  will  start  
and run normally. 

 
 
 

10  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: