background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

The  tests  outlined  above  are  for  common  
applications  of  compressors  in  this  family.  Many  
other  applications  of  the  compressor  exist,  and  
tests  to  insure  those  designs  can

’t  possibly  

be  covered  in  this  bulletin.  Please  consult  with  
Application  Engineering  on  applications  outside  of  
those  outlined  above  for  the  appropriate  application  
tests. 

ASSEMBLY  LINE  PROCEDURES 

Installing the Compressor 

WARNING 

Use care and the appropriate material handling 
equipment when lifting and moving compressors. 
Personal safety equipment must be used. 

Copeland   Scroll   compressors   leave   the   factory  
dehydrated  and  with  a  positive  dry  air  charge.  Plugs  
should  not  be  removed  from  the  compressor  until  the  
compressor  has  had  sufficient  time  to  warm  up  to  the  
factory  ambient,  if  the  compressor  is  stored  outside  in  a  
cold  climate. The  suggested  warm  up  time  is  one  hour  
per  4°F  (2K)  difference  between  outdoor  and  indoor  
temperature.  It  is  suggested  that  the  larger  suction  
plug  be  removed  first  to  relieve  the  internal  pressure.  
Removing  the  smaller  discharge  plug  could  result  in  a  
spray of oil out of this fitting since some oil accumulates  
in  the  head  of  the  compressor  after  Emerson

’s  run  

test.  The  inside  of  both  fittings  should  be  wiped  with  
a  lint free cloth  to remove residual  oil  prior  to  brazing.  
A  compressor  containing  POE  oil  should  never  be  left  
open longer than 5 minutes. 

Assembly Line Brazing Procedure 

WARNING 

Personal  safety  equipment  must  be  used  during 
brazing operation. Heat shields should be 
used  to  prevent  overheating  or  burning  nearby  
temperature 

sensitive 

parts. 

Fire 

extinguishing  

equipment  should  be  accessible  in  the  event  of  a  
fire. 

Figure  8  discusses  the  proper  procedures  for  brazing  
the suction and discharge lines to a scroll compressor. 
NOTICE    It  is  important  to  flow  nitrogen  through  the  
system  while  brazing  all  joints  during  the  system  
assembly  process.  Nitrogen  displaces  the  air  and  
prevents  the  formation  of  copper  oxides  in  the  system.  
If  allowed  to  form,  the  copper  oxide  flakes  can  later  
be  swept  through  the  system  and  block  screens  such  
as  those  protecting  capillary  tubes,  thermal  expansion  
valves,  and  accumulator  oil  return  holes.  Any  blockage  
of  oil  or  refrigerant  may  damage  the  compressor  
resulting in failure. 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

Pressure Testing 

WARNING 

Never  pressurize  the  compressor  to  more  than  
350 psig (24 bar) for leak checking purposes. 
Never  pressurize  the  compressor  from    a  nitrogen 
cylinder or other pressure source without an 
appropriately  sized  pressure  regulating  and  relief 
valve. 

The pressure used on the line to meet the UL burst 
pressure  requirement  must  not  be  higher  than  350 
psig (24 Bar). Higher pressure may result in permanent 
deformation  of  the  compressor  shell  and  possible 
misalignment or bottom cover distortion. 

Assembly Line System Charging Procedure 

Systems should be charged with liquid on the high side  
to the extent possible. The majority of the charge should  
be pumped in the high side of the system to prevent low  
voltage  starting  difficulties,  hipot  failures,  and  bearing  
washout during the first-time start on the assembly line.  
If  additional  charge  is  needed,  it  should  be  added  as  
liquid  to  the  low  side  of  the  system  with  the  compressor  
operating.  Pre-charging  on  the  high  side  and  adding  
liquid on the low side of the system are both meant to  
protect  the  compressor  from  operating  with  abnormally  
low  suction  pressures  during  charging.  NOTICE    Do  
not  operate  the  compressor  without  enough  system  
charge  to  maintain  at  least  20  psig  (1.4  bar)  suction  
pressure.  Do  not  operate  the  compressor  with  the  
low  pressure  cut-out  disabled.  Do  no  operate  with  
a  restricted  suction  or  liquid  line.  Depending  on  the  
discharge pressure, allowing pressure to drop below 
20 psig (1.4 bar) for more than a few  seconds may  
overheat  the  scrolls  and  cause  early  drive  bearing  
damage.  NOTICE    Do  not  use  the  compressor  to  
test the opening set point of a high pressure cutout. 
Bearings  are  susceptible  to  damage  before  they  have  
had several hours of normal running for proper break in. 

“Hipot” (AC High Potential) Testing 

CAUTION 

Use  caution  with  high  voltage  and  never  hipot 
when compressor is in a vacuum. 

Copeland  Scroll  compressors  are  configured  with  the  
motor  down  and  the  pumping  components  at  the  top  
of  the  shell.  As  a  result,  the  motor  can  be  immersed  
in  refrigerant  to  a  greater  extent  than  hermetic  
reciprocating  compressors  when  liquid  refrigerant  is  
present in the shell. In this respect, the scroll is more  
like  semi-hermetic  compressors  that  have  horizontal  
motors  partially  submerged  in  oil  and  refrigerant. When  
Copeland Scroll compressors are hipot tested with 

 
 

12  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: