background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

liquid refrigerant in the shell, they can show higher levels 
of  leakage  current  than  compressors  with  the  motor  on 
top.  This  phenomenon  can  occur  with  any  compressor 
when the motor is immersed in refrigerant. The level of 
current  leakage  does  not  present  a  safety  issue.  To 
lower  the  current  leakage  reading,  the  system  should 
be  operated  for  a  brief  period  of  time  to  redistribute 
the  refrigerant  to  a  more  normal  configuration  and  the 
system  hipot  tested  again.  See  AE4-1294  for  megohm 
testing  recommendations.  Under  no  circumstances 
should    the    hipot    test    be    performed    while    the 
compressor is under a vacuum. 

Final Run Test 

Customers  that  use  a  nitrogen  final  run  test  must 
be careful to not overheat the compressor. Nitrogen is 
not  a  good  medium  for  removing  heat  from  the 
compressor,  and  the  scroll tips  can  be  easily  damaged 
with  high  compression  ratios  and/or  long  test  times. 
Copeland  Scroll  compressors  are  designed  for  use 
with refrigerant, and testing with nitrogen may result in a 
situation  where  the  compressor  does  not  develop  a 
pressure  differential  (no  pump  condition).  When  testing 
with  nitrogen,  the  compressor  must  be  allowed  to  cool 
for several minutes between tests. 

Single  phase  scrolls  with  an  electrical  nomenclature  
of 

“PFV” (208-230 volt, 1Ø, 60 Hertz) at the end of the  

model  number  are  guaranteed  to  start  at  187  volts  or  
higher and must have a voltage no lower than 197 volts  
once  the  compressor  is  running  under  load.  All  other  
compressor voltages, both single and three phase, 50 & 
60 Hertz are guaranteed to start and run at 10% below 
the lowest voltage shown on the nameplate. 

Variable  transformers  used  on  assembly  lines  are  often  
incapable  of  maintaining  the  starting  voltage  when  
larger  compressors  are  tested.  To  test  for  voltage  sag  
during  starting,  the  first  compressor  in  a  production  
run should be  used  to preset  the  voltage.  Remove  the  
start  wire  from  the  compressor  and  apply  200  volts  to  
the  compressor.  With  the  start  winding  removed,  the  
compressor  will  remain  on  locked  rotor  long  enough  
to  read  the  supply  voltage.  If  the  voltage  sags  below  
the  minimum  guaranteed  starting  voltage,  the  variable  
transformer  must  be  reset  to  a  higher  voltage.  When  
discussing  this  starting  amperage  it  should  be  noted  
that 

“inrush current”  and  locked rotor  amps (LRA)  are  

one  and  the  same.  The  nameplate  LRA  is  determined  
by  physically  locking  a  compressor  and  applying  the  
highest  nameplate  voltage  to  the  motor.  The  amperage  
that the motor draws after four seconds is the value that  
is used on the nameplate. Since there is a direct ratio  
between  voltage  and  locked  rotor  amperage,  the  lower  
the line  voltage  used  to start  the compressor, the  lower  
the locked rotor amperage will be. 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

Unbrazing System Components 

WARNING 

Before attempting to braze, it is important to recover 
all refrigerant from both the high and low side of the 
system. 

If  the  refrigerant  charge  is  removed  from  a  scroll- 
equipped  unit  by  recovering  one  side  only,  it  is  very  
possible that either the high or low side of the system  
remains  pressurized.  If  a  brazing  torch  is  then  used  
to  disconnect  tubing,  the  pressurized  refrigerant  and  
oil  mixture  could  ignite  when  it  escapes  and  contacts  
the  brazing  flame.  Instructions  should  be  provided  
in  appropriate  product  literature  and  assembly  (line  
repair)  areas.  If  compressor  removal  is  required,  the  
compressor  should  be  cut  out  of  the  system  rather  
than  unbrazed.  See  Figure  8  for  proper  compressor  
removal procedure. 

SERVICE PROCEDURES 

Copeland Scroll Compressor Functional Check 

A  functional  compressor  test  during  which  the  suction 
service valve is closed to check how low the compressor 
will pull the suction pressure is not a good indication of 
how well a compressor is performing. NOTICE Such a 
test  will  damage  a  scroll  compressor  in  a  few 
seconds.  The  following  diagnostic  procedure  should  be 
used to evaluate whether a Copeland Scroll compressor 
is functioning properly: 

1.  Proper voltage to the unit should be verified.  

2. Determine if the internal motor overload has 

opened  or  if  an  internal  motor  short  or  ground 
fault  has  developed.  If  the  internal  overload  has 
opened,  the  compressor  must  be  allowed  to  cool 
sufficiently to allow it to reset. 

3.  Check that the compressor is correctly wired.  

4. Proper indoor and outdoor blower/fan operation 

should be verified. 

5.  With service gauges connected to suction and 

discharge pressure fittings, turn on the compressor. 
If  suction  pressure  falls  below  normal  levels  the 
system is either low on charge or there is a flow 
blockage in the system. 

6.  Single phase compressors - If the compressor 

starts and the suction pressure does not drop 
and  discharge  pressure  does  not  rise  to  normal  
levels,  either  the  reversing  valve  (if  so  equipped)  
or  the  compressor  is  faulty.  Use  normal  diagnostic  
procedures  to  check  operation  of  the  reversing  
valve.  Three  phase  compressors  -  If  suction  
pressure does not drop and discharge pressure 

 
 

13  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: