background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

Introduction 

The  ZR*K5  Copeland  Scroll

  compressors  are  

designed  for  residential  and  light  commercial  R-407C  
air-conditioning  and  heat  pump  applications  and  R-22  
service applications. A typical model number is ZR28K5- 
PFV.  This  bulletin  describes  the  operating  characteristics,  
design  features  and  application  requirements  for  these  
models.  For  additional  information,  please  refer  to  Online  
Product  Information  accessible  from  our  website  at  
www.emersonclimate.com.  Operating  principles  of  the  
Copeland Scroll compressor are described  in  Figure 9 at  
the end of this bulletin. The scroll compressors outlined  
in this bulletin range in size from 14,650 Btu/hr to 53,500  
Btu/hr (4.3 - 15.7 kW) and include common 50 and 60  
Hertz, single and three phase voltages. 

The  models  include  a  number  of  features  outlined  in 
the matrix below. 

Nomenclature 

The model numbers of the Copeland Scroll compressors 
include  the  approximate  nominal  60  Hz  capacity  at 
standard    operating    conditions.  An    example    would 
be  the  ZR28K5-TFD,  which  has  28,400  Btu/hr  (8.3 
kW)  cooling  capacity  at  the  ARI  high  temperature  air 
conditioning  rating  point  when  operated  at  60  Hz.  Note 
that  the  same  compressor  will  have  approximately  5/6 
of this capacity or 23,300 Btu/hr (6.8 kW) when operated 
at 50 Hz. Please refer to Online Product Information at 
www.emersonclimate.com for details. 
 
Application Considerations 

The   following   application   guidelines   should   be 
considered  in  the  design  of  a  system  using  ZR*K5 
scroll  compressors.   Some  of  this  information  is 
recommended,  whereas  other  guidelines  must  be 
followed.  The  Application  Engineering  department  will 
always  welcome  suggestions  that  will  help  improve 
these types of documents. 

Internal Pressure Relief (IPR) Valve 

The  internal  pressure  relief  valve  is  located  between  

the  high  and  low side  of the compressor.  It  is  designed  
to  open  when  the  discharge-to-suction  pressure  
differential exceeds 375 to 450 psid (26-31 bar). When 

 

the valve opens, hot discharge gas is routed  back into  
the area of the motor protector to cause a trip. During  
fan  failure  testing,  system  behavior  and  operating  
pressures will depend on the type of refrigerant metering  
device.  Fixed  orifice  devices  may  flood  the  compressor  
with  refrigerant,  and  thermostatic  expansion  devices  
will  attempt  to  control  superheat  and  result  in  higher  
compressor  top  cap  temperatures.  Fan  failure  testing  
or  loss of  air flow  in  both cooling  and  heating should  
be evaluated by the system designer to assure that the  
compressor  and  system  are  protected  from  abnormally  
high pressures. 

Discharge Temperature Protection 

CAUTION 

Compressor  top  cap  temperatures  can  be  very  
hot. Care must be taken to ensure that wiring or 
other  materials  which  could  be  damaged  by  these 
temperatures  do  not  come  into  contact  with  these 
potentially hot areas. 

The  Therm-O-Disc

™ or TOD is a temperature-sensitive  

snap  disc  device  located  on  the  muffler  plate.  It  is  
designed  to  open  and  route  excessively  hot  discharge  
gas  back  to  the  motor  protector  when  the  internal  
discharge gas exceeds 290°F (144°C). During a situation  
such as loss of charge, the compressor will be protected  
for some time while it trips the protector. However, as  
refrigerant  leaks  out,  the  mass  flow  and  the  amperage  
draw are reduced and the scrolls will start to overheat. A  
low pressure control is recommended for loss of charge  
protection  for  the  highest  level  of  system  protection.  
The  low  pressure  cut-out  can  provide  protection  against  
indoor  blower  failure  in  cooling,  outdoor  fan  failure  in  
heating,  closed  liquid  or  suction  line  service  valves,  
or  a  blocked  liquid  line  screen, filter,  orifice,  or TXV.  
All  of  these  can  starve  the  compressor  of  refrigerant  
and  result  in  compressor  failure.  The  low  pressure  
cut-out  should  have  a  manual  reset  feature  for  the  
highest  level  of  system  protection.  If  a  compressor  is  
allowed to cycle after a fault is detected, there is a high  
probability  that  the  compressor  will  be  damaged  and  
the  system  contaminated  with  debris  from  the  failed  
compressor  and  decomposed  oil.  If  current  monitoring  
of  the  compressor  is  available,  the  system  controller  
can take advantage of the compressor TOD and internal 

 
 

Model 

 

Motor 

Application  

Frame Size*  

AC  

HP 

 

Quiet 

IPR 

TOD 

Shutdown 

 

Discharge 

Motor 

Electrical  

Check Valve Protector  

Connections  

ZR16-32K5 

53 

Molded Plug 

ZR38-54K5 

63 

Molded Plug 

* Approximate Shell Diameter (e.g. 53 = 5.5" and 63 = 6.5")  

 

 

© 2013 Emerson Climate Technologies, Inc. 

Printed in the U.S.A.  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: