background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

since  the  overload  protector  setting  could  be  affected.  
R-407C may only  be used  with compressors tested and  
approved  for  use  with  R-407C  and  that  contain  polyol  
ester  (POE)  oil.  Compressors  containing  POE  oil  have  
an 

“E” in the seventh place of the model number, e.g.  

ZR28K5E-PFV. 

Power Supply 

All  motors for  the  Copeland  Scroll  compressors  covered 
in  this  bulletin,  whether  single  or  three  phase,  with  the 
exception  of  the 

“PFV” 208-230, 1Ø, 60 Hz motor, are 

designed to operate  within a voltage range of +/-10% of 
the  voltages  shown  on  the  nameplate.  For  example,  a 
compressor  with  a  nameplate  voltage  of  200-230  volts 
can  start  and  operate  within  a  range  of  180-253  volts. 
Compressors  with  a 

“PFV”  designated  motor  such  as 

ZR54K5-PFV, may  only  be  operated  in  a range  of 197- 
253 volts under maximum load conditions. 

Accumulators 

The  use  of  accumulators  is  very  dependent  on  the  
application.  The  Copeland  Scroll  compressor

’s  inherent  

ability  to  handle  liquid  refrigerant  during  occasional  
operating  flood  back  situations  make  the  use  of  an  
accumulator  unnecessary  in  standard  designs  such  as  
condensing  units.  Applications  such  as  heat  pumps  with  
orifice  refrigerant  control  that  allow  large  volumes  of  
liquid refrigerant  to flood  back to  the compressor  during  
normal  steady  operation  can  dilute  the  oil  to  such  an  
extent  that  bearings  are  inadequately  lubricated,  and  
wear  will  occur.  In  such  a  case  an  accumulator  must  
be  used  to  reduce  flood  back  to  a  safe  level  that  the  
compressor  can  handle.  Heat  pumps  designed  with  
a  TXV  to  control  refrigerant  during  heating  may  not  
require  an  accumulator  if  testing  assures  the  system  
designer that there  will  be  no flood  back throughout the  
operating  range.The  accumulator  oil  return  orifice  should  
be  from  0.040  to  0.055  inches  (1  -  1.4mm)  in  diameter  
depending  on  compressor  size  and  compressor  flood  
back  results.  A  large-area  protective  screen  no  finer  than  
30x30  mesh  (0.6mm  openings)  is  required  to  protect  
this small orifice from plugging. Tests have shown that  a  
small screen with a fine mesh can easily become plugged  
causing  oil  starvation  to  the  compressor  bearings.  The  
size  of  the  accumulator  depends  upon  the  operating  
range of the system and the amount of subcooling and  
subsequent  head  pressure  allowed  by  the  refrigerant  
control.  System  modeling  indicates  that  heat  pumps  
that  operate  down  to  and  below 0°F  (-18°C)  will  require  
an  accumulator  that  can  hold  around  70%  to  75%  of  
the  system  charge.  Behavior  of  the  accumulator  and  
its  ability  to  prevent  liquid  slugging  and  subsequent  oil  
pump-out  at  the  beginning  and  end  of  the  defrost  cycle  
should  be  assessed  during  system  development.  This  
will require special accumulators and compressors with 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

sight tubes and/or sight glasses for monitoring refrigerant 
and oil levels. 

Charge Compensators 

Charge  compensators  are  devices  that  store  excess  
refrigerant  during  the  heating operation  of  a  heat  pump  
with  a  TXV  refrigerant control.  Unlike  an  orifice,  a TXV  
will  not  allow  excessive  refrigerant  to  flood  back  to  
the  compressor.  This  means  that  the  excess  system  
refrigerant  will  either  have  to  back  up  in  the  indoor  
coil  during  heating,  causing  high  head  pressure,  or  
be  stored  in  a  charge  compensator  until  needed.  A  
charge  compensator  is  normally  a  hollow  vessel  with  
only  one  opening  that  is  attached  to  the  vapor  line.  
The shell is usually attached to the outdoor coil or has  
a line from the outdoor coil running through it for extra  
cooling  during  heating  and  to  drive  the  refrigerant  out  
during the cooling cycle. The size is dependent on how  
much  refrigerant  has  to  be  removed  from  the  system  
throughout the system operating map. 

Screens 

Screens  finer  than  30x30  mesh  (0.6  mm  openings)  
should not be used anywhere in the system with these  
compressors.  Field  experience  has  shown  that  finer  
mesh  screens  used  to  protect  thermal  expansion  
valves,  capillary  tubes,  or  accumulators  can  become  
temporarily  or  permanently  plugged  with  normal  system  
debris and block the flow of either oil or refrigerant to the  
compressor.  Such  blockage  can  result  in  compressor  
failure. 

Crankcase Heat - Single Phase 

A  crankcase  heater  is  recommended  on  single  phase  
compressors  when  the  system  charge  is  over  the  
charge  limit  shown  in  Table  4.  A  crankcase  heater  is  
required for systems containing more  than 120%  of the  
compressor  refrigerant  charge  limit  listed  in  Table  4.  
This  includes  long  line  length  systems  where  the  extra  
charge  will  increase  the  standard  factory  charge  above  
the 120% limit. 

Experience  has  shown  that  compressors  may  fill  with  
liquid  refrigerant  under  certain  circumstances  and  
system configurations, notably after long off cycles when  
the  compressor  has  cooled.  This  may  cause  excessive  
start-up clearing  noise;  or the compressor may  start  and  
trip  the  internal  overload  protector  several  times  before  
running. The  addition  of a crankcase  heater  will reduce  
customer  noise  and  dimming  light  complaints  since  
the compressor will  no  longer have  to clear out liquid  
during  starting.  Table  5  lists  the  crankcase  heaters  
recommended for the various models and voltages. 
WARNING!    Crankcase  heaters  must  be  properly  
grounded. To properly install the crankcase heater, the 

 
 

6  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: