8 • Maintenance
1.16. Maintenance
Use the following procedures to perform simple
maintenance tasks on the ISIS controller.
1.16.1.Filter Maintenance
Following the construction phase, and then on a quar-
terly (minimum) basis, the air filter on the fan intake
should be either:
• Replaced, or
• Cleaned
To clean or replace the air filter, remove the two
screws that secure the intake grill. Lift the grill away from
the unit and remove the filter. Clean the filter by washing
it with warm, soapy water and thoroughly rinsing and dry-
ing it before replacing. Replace the filter, then fasten the
intake grill securely.
Regular filter maintenance promotes cooler internal
temperature and longer equipment life. If the ISIS has Nia-
gara Release 2.2 or higher, its main board temperature
under the CPU (and other internal variables) can be moni-
tored by the station running on it.
1.16.2.Real-Time Clock Battery
The Central Processor Card of the ISIS is equipped
with a 3.0VDC Lithium battery. The battery provides
back-up power to the Real-Time Clock and the CMOS
data area that stores the BIOS setup information. The
design life of the battery is 10 years. Replacement of the
battery requires removal of the Central Processor Card and
re-entry of the setup information.
1.17. Replacement Parts
Servicing the ISIS may call for replacement parts.
There are three categories of parts:
• Non-replaceable
• Standard Replacement
• Field Replacement
1.18. Non-Replaceable Parts
Other than the parts listed in the replacement parts
section, there are no serviceable components on an ISIS.
1.18.1.Memory
Any addition, modification, or replacement of mem-
ory components requires software configuration and is not
a field upgrade.
1.18.2.Fuses
An internal 5
x
20 mm, Slo-Blo fuse rated at 1.25A,
250VAC (domestic) or 0.75A, 250VAC (international) is
used for power circuit protection. This circuitry is not
user-serviceable. If the power circuitry is suspect, contact
the factory for replacement (field replacement will void
the ISIS warranty).
NOTE: Alternately, after the construction
phase is complete, you can remove the ISIS
air filter. This is recommended only for
installations with a high exposure to heat
(average temperature close to 95ºF (35ºC), and where
the ISIS environment remains continuously clean.
NOTE: Consult with CPC before changing
the battery in the ISIS.
NOTE: For all replacement part numbers,
contact CPC at 1-800-829-2724.
NOTE: For additional information on modi-
fying the memory capacity of the ISIS, con-
sult CPC for technical support at 1-800-829-
2724.