background image

1598024314 XR30CX VST GB r3.1 05.10.2015.doc 

XR30CX

 

2/4 

6. MAIN FUNCTIONS

6.1

 

HOW TO SEE THE SETPOINT 

1.

Push and immediately release the SET button: the display will show the 
Set point value; 

2.

Push and immediately release the SET button or wait for 5 seconds to 
display the probe value again. 

6.2

 

HOW TO CHANGE THE SETPOINT 

1.

Keep SET button pressed more than 2 seconds to change the Set point value.

2.

The value of the set point will be displayed and the “°C or “°F” LED icon will start blinking.

3.

To change the Set-point value, push the UP or DONW buttons within 10s.

4.

To memorise the new set point value, push the SET button again or wait for 10s.

6.3

 

HOW TO START A MANUAL DEFROST 

Push the DEF key for more than 2 seconds and a manual defrost will start. 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

To change any parameter value, operate as follows:  
1. Enter  the  Programming  mode  by  pressing  SET  +  DOWN  for 3s (the “°C” or “°F” LED icons will 

start blinking). 

2. Select the required parameter. Press SET to display its value.
3. Use UP or DOWN to change its value.
4. Press SET to store the new value and move to the following parameter.

To exit: Press SET + UP or wait for 15s without pressing any key. 
NOTE: the set value is stored even when the procedure is exited by waiting for the time-out to expire. 

6.5

 

THE HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

1. Enter  the  Programming  mode  by  pressing  SET  +  DOWN  for 3s (the “°C” or “°F” LED icons will 

start blinking). 

2. Released the buttons and then push again them (SET + DOWN) for more than 7s. The Pr2 label 

will be displayed immediately, followed from the HY parameter.
Now it is possible to browse the hidden menu.

3. Select the required parameter.
4. Press SET to display its value 
5. Use UP or DOWN to change its value.
6. Press SET to store the new value and move to the following parameter.

To exit: Press SET + UP or wait for 15s without pressing any key. 

NOTE1:  if  no  parameter  is  present  in  Pr1,  after  3s  the  “noP”  message  will be displayed. Keep the 
buttons pushed till the Pr2 message will be displayed.  
NOTE2:  the  set  value  is  stored  even  when  the  procedure  is  exited  by  waiting  for  the  time-out  to 
expire. 

6.5.2  HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing 
SET + DOWN buttons. If a parameter is part of the user level, when showed in the hidden menu the 
decimal point will be lit. 

6.6

 

HOW TO LOCK THE KEYBOARD 

1.

Keep pressed for more than 3 s the UP + DOWN buttons.

2.

The  “PoF”  message  will  be  displayed  and  the  keyboard  will  be  locked.  At  this  point  it  will  be 
possible only to see the set point or the MAX o Min temperature stored 

3.

If a button is pressed more than 3s the “PoF” message will be displayed.

6.7

 

TO UNLOCK THE KEYBOARD 

Keep pressed both UP and DOWN for more than 3s till the “Pon” message will be displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When  defrost  is  not  in  progress,  it  can  be  activated  by  keeping the UP button pressed for about 3 
seconds.  The  compressor  operates  to  maintain the CCS set point for the time set through the CCt 
parameter.  The  cycle  can  be  terminated  before  the  end  of  the  set  time  using  the  same  activation 
button (UP for 3 seconds). 

6.9

 

THE ON/OFF FUNCTION 

When “onF=oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF 
message is displayed. In this configuration, the regulation is disabled. 
To switch the instrument on, push again the ON/OFF key. 

WARNING:  Loads  connected  to  the  normally  closed  contacts  of  the  relays  are  always 
supplied and under voltage, even if the instrument is in stand by mode.  

7. PARAMETERS

REGULATION 

HY 

Differential:  (0.1÷25.5°C;  1÷255°F)  intervention  differential  for  set  point. 
Compressor Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the 
temperature reaches the set point. 

LS  

Minimum set point: (-100°C÷SET; -148°F÷SET) it sets the minimum value for the 
set point. 

US 

Maximum set point: (SET÷150°C; SET÷302°F) it sets the maximum value for set 
point. 

ot  

Thermostat  probe  calibration:  (-12.0÷12.0°C;  -120÷120°F)  allows  to  adjust 

possible offset of the thermostat probe. 

odS 

Outputs  activation  delay  at  start  up: (0÷255min)  this  function  is  enabled  at  the 
initial  start  up  of  the  instrument  and  inhibits  any  output  activation  for  the  period  of 
time set in the parameter.  

AC  

Anti-short  cycle  delay:  (0÷50min)  minimum  interval  between the compressor stop 
and the following restart. 

rtr 

Percentage of the second and first probe for regulation: (0÷100; 100=P1, 0=P2) 
it  allows  to  set  the  regulation  according  to  the  percentage  of  the  first  and  second 
probe, as for the following formula (rtr(P1-P2)/100 + P2). 

CCt 

Compressor  ON  time  during  continuous  cycle:  (0.0÷24h00min,  res.  10min) 
allows  to  set  the  length  of  the  continuous  cycle.  Compressor  stays  on  without 
interruption during CCt time. This is useful, for instance, when the room is filled with 
new products. 

CCS 

Set  point  for  continuous  cycle:  (-100÷150°C;  -148÷302°C)  it  sets  the  set  point 
used during the continuous cycle. 

Con 

Compressor  ON  time  with  faulty  probe:  (0÷255min)  time  during  which  the 
compressor  is  active  in  case  of faulty thermostat probe. With Con=0 compressor is 
always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:  (0÷255min)  time  during  which  the 
compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With  CoF=0  compressor  is 
always active. 

CH 

Type of action: (CL, Ht) CL = cooling; Ht = heating. 

DISPLAY 

CF 

Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.  
WARNING: When the measurement unit is changed the SET point and the values of 
the parameters HYLSUSotALU and ALL have to be checked and modified (if 
necessary). 

rES 

Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display. 

dLY 

Display  delay:  (0.0÷20min00s;  res.  10s)  when  the  temperature  increases,  the 
display is updated of 1°C or 1°F after this time. 

DEFROST 

idF 

Interval  between  defrost  cycles:  (0÷120hours)  determines  the  interval  of  time 
between two defrost cycles. 

MdF 

(Maximum) length for defrost: (0÷255min)  
When P2P=n, (not evaporator probe: timed defrost) it sets the defrost duration.  
When  P2P=Y  (defrost  end  based  on  temperature)  it  sets  the  maximum  length  for 
defrost. 

dFd 

Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;  
it = temperature at defrost start; SEt = set point; dEF = “dEF” label. 

dAd 

MAX display delay after defrost: (0÷255min) sets the maximum time between the 
end of defrost and the restarting of the real room temperature display. 

ALARMS 

ALC  

Temperature  alarms  configuration:  (Ab;  rE)  Ab  =  absolute  temperature,  alarm 
temperature is given by the ALL or ALU values.  rE = temperature alarms are referred 
to  the  set  point.  Temperature  alarm  is  enabled  when  the  temperature  exceeds  the 
[SET+ALU] or [SET-ALL] values. 

ALU 

MAXIMUM temperature alarm: 

 

ALC=Ab: (SET÷150°C; SET÷302°F)

 

ALC=rE: (0.1÷50°C; 1÷90°F)

When  this  temperature  is  reached,  the  alarm  is  enabled,  possibly  the  ALd  delay 

time. 

ALL 

Minimum temperature alarm:  

 

ALC=Ab: (-100.0 ÷ SET°C; -148÷302°F)

 

ALC=rE: (0.1÷50°C; 1÷90°F)

When this temperature is reached, the alarm is enabled, possibly the ALd delay time.

AFH 

Differential  for  temperature  alarm  recovery:  (0.1÷25.5°C;  1÷45°F)  intervention 
differential for recovery of temperature alarm. 

ALd 

Temperature  alarm  delay:  (0÷255  min)  time  interval  between  the  detection  of  an 
alarm condition and alarm signalling. 

dAo 

Exclusion  of  temperature  alarm  at  start-up:  (0.0÷23h  50min,  res.  10min)  time 
interval  between  the  detection  of  the  temperature  alarm  condition  after  instrument 
power on and alarm signalling. 

ALARM RELAY MANAGEMENT –FOR BATTERY-BACKUP MODELS (7020122 and 7020202) 

tbA 

Alarm relay silencing (with oA1=ALr): (n, Y) 
= silencing disabled; alarm relay stays on till alarm condition lasts.  
Y  =  silencing  enabled;  alarm  relay  is  switched  OFF  by  pressing  a  key  during  an 
alarm. 

Aro 

Alarm relay activation with power failure: (n, Y) 
= the alarm relay is never activated during a power failure. 
= the alarm relay is activated during a power failure. 

ALF 

Alarm relay activation for all the alarms: (n, Y) 
n
  =  the  alarm  relay  is  activated  only  in  case  of  a  temperature  alarm  or  regulation 
probe failure. 
Y = the alarm relay is activated for all the alarms. 

bon 

Time of buzzer restart after muting, in case of alarm duration: (0÷30min) when 
0 the buzzer is always off after muting. 

AoP 

Alarm  relay  polarity:  it  set  if  the  alarm  relay  is  open  or  closed  when  an  alarm 
happens. CL= terminals 1-2 closed during an alarm; oP = terminals 1-2 open during 
an alarm 

DIGITAL INPUT  

i1P 

Digital  input  polarity:  (oP;  CL)  oP  =  the  digital  input  is  activated  by  opening  the 
contact; CL = the digital input is activated by closing the contact. 

i1F 

Digital input configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES)  
EAL  =  external  alarm:  “EA”  message  is  displayed;  bAL  =  serious  alarm  “CA” 
message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor 
=  door  switch  function;  dEF  =  activation  of  a  defrost  cycle;  AUS  =to  switch on the 
second relay if oA1 = AUS; Htr = kind of action inversion (cooling – heating); FAn = 
not set it; ES 
= Energy saving. 

Summary of Contents for Dixel XR30CX Series

Page 1: ... point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper Compr SET ON In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters Con and CoF 3 2 DEFROST Defrost is performed through a simple stop of the compressor Parameter idF controls the interval between defrost cycle...

Page 2: ...in minimum interval between the compressor stop and the following restart rtr Percentage of the second and first probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24h00min res 10min allows to set the length of the continuous...

Page 3: ...The temperature range allowed for correct operation is 0 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulate by the cooling holes 11 ELECTRICAL CONNECTIONS The instrument is provided with screw terminal block to connect cables with a cross section up to 2 5mm2 Before connecting cables make sure the pow...

Page 4: ...res 10s 0 0 0 0 Pr2 idF Interval between defrost cycles 1 120 hours 0 0 Pr1 MdF Maximum length for defrost 0 255 min 0 0 Pr1 dFd Displaying during defrost rt it SEt DEF rt rt Pr2 dAd MAX display delay after defrost 0 255 min 0 0 Pr2 ALC Temperature alarms configuration rE related to set Ab absolute rE rE Pr2 ALU MAXIMUM temperature alarm Set 110 C Set 230 F 15 C 59 F 15 C 59 F Pr1 ALL Minimum temp...

Reviews: